Use case · New single-family house

Electrical plan for a new single-family house: room by room (NEC 2023)

Building a new house? Its electrical plan starts from the rooms: receptacles every 6 ft of wall, countertops every 24 in, a switched light in each room, smoke alarms in every bedroom. Then come the required circuits (two 20 A small-appliance, laundry, bathroom, garage), the 240 V appliances and a 200 A panel. Here is what goes where in a typical 3-bedroom, 2-bath home of about 1,800 ft², under NEC 2023.

Updated on Last checked NEC (NFPA 70) 2023

Key facts

  • 01Required 20 A circuits: at least 2 small-appliance circuits (kitchen, pantry, dining), laundry, bathroom and garage (210.11(C)).
  • 02General lighting is sized at 3 VA per ft²: 1,800 ft² gives 5,400 VA, so at least 3 general circuits at 15 A (220.41, 210.11(A)).
  • 03GFCI on kitchen, bathroom, garage, outdoor, laundry and basement receptacles; AFCI on 120 V circuits of bedrooms, living areas, kitchen, hallways, closets and laundry.
  • 04Service at least 100 A; 200 A is the usual choice for a new house, with an outdoor emergency disconnect and surge protection.
  • 05Smoke alarms in each bedroom, outside each sleeping area and on each story, hard-wired and interconnected (IRC R314).

Before you draw: which code applies to your lot

This page uses NEC 2023 and the IRC 2024 electrical chapters (which follow it) as the reference. Where a value is uncertain or often amended locally, it says so.

The example: a 3-bedroom, 2-bath house with an attached garage

A single-story home of about 1,800 ft²: an open kitchen with an island and a dining area, a living room, three bedrooms with closets, a hall bathroom and a primary bathroom, a laundry room, a hallway, and an attached two-car garage. Cooking and water heating are electric, heating and cooling come from a heat pump, and the garage is ready for an EV charger. Smoke and CO alarm rules apply (the attached garage alone triggers CO alarms).

Room by room: what goes where (NEC 2023, IRC R314 / R315)
RoomReceptaclesLighting and alarmsProtection / circuit
Living roomNo point along a wall more than 6 ft from a receptacle (wall spaces 2 ft or wider)Wall-switched lighting outlet (or a switched receptacle)AFCI; general 15 / 20 A circuit
KitchenCountertop: no point more than 24 in from a receptacle, each counter space 12 in or wider; island: receptacle optional, but a provision (box / raceway) for a future oneWall-switched lighting outlet (a switched receptacle is not enough)GFCI on all receptacles + AFCI; 2 × 20 A small-appliance circuits
Dining area6 ft wall ruleSwitched lighting outletOn the small-appliance circuits; AFCI
Bedrooms (×3)6 ft wall ruleSwitched lighting outlet; smoke alarm in eachAFCI; general circuits
Bathrooms (×2)At least one within 3 ft of each basinSwitched lighting outlet; exhaust fanGFCI; 20 A bathroom circuit
HallwayOne receptacle if 10 ft or longerSwitched light, 3-way at both ends; smoke alarm outside the bedrooms, CO alarmAFCI
LaundryAt least one receptacle for the washerSwitched lighting outletGFCI + AFCI; 20 A laundry circuit; 30 A 240 V dryer circuit
GarageAt least one per vehicle bay, no higher than 5.5 ftSwitched lighting outletGFCI; 20 A garage circuit; EV circuit
OutdoorsOne at the front and one at the back, no higher than 6 ft 6 in above grade; one on each deck or porch accessible from insideSwitched light at each outdoor entranceGFCI; weather-resistant with in-use covers
Receptacles are tamper-resistant throughout (406.12). Room rules: NEC 210.52, 210.70(A), 210.8(A), 210.12(A); alarms: IRC R314 / R315.

The branch circuits of a typical new house

Typical circuit list for the example house (copper, NM-B)
CircuitBreaker / wireNotes
General lighting15 A / 14 AWGAt least 3 general circuits for 5,400 VA (3 VA/ft²); AFCI in habitable rooms
General receptacles20 A / 12 AWG (15 A / 14 AWG acceptable)Living room, bedrooms, hallway; AFCI
Small-appliance (×2)20 A / 12 AWGKitchen countertop, pantry and dining receptacles only; dual-function GFCI / AFCI
Bathroom20 A / 12 AWGBathroom receptacles only (or everything in one bathroom); GFCI
Laundry20 A / 12 AWGLaundry receptacles only; GFCI + AFCI
Garage20 A / 12 AWGGarage receptacles, may also serve outdoor receptacles; GFCI
Range40 A / 8 AWG, 240 V two-pole4-wire, NEMA 14-50R; 50 A / 6 AWG for a range over 12 kW
Dryer30 A / 10 AWG, 240 V two-pole4-wire, NEMA 14-30R
Water heater30 A / 10 AWG, 240 V two-pole4,500 W element, sized at 125 %
Dishwasher, disposal15 or 20 AOften a shared 20 A circuit if the manufacturer allows; dishwasher GFCI
Over-the-range microwave20 ADedicated per the manufacturer's instructions (common practice)
Heat pump / ACPer nameplate MCA / MOCP, 240 V two-poleFurnace or air handler on its own 120 V or 240 V circuit
EV charger40 A / 8 AWG for a 32 A chargerIndividual circuit, breaker at least 125 % of the charger rating (625.40)
Appliance GFCI: NEC 2023 extends GFCI to ranges, ovens, cooktops, dryers and microwaves (210.8(D), 422.5(A)), but many AHJs have amended ranges and dryers out. Check locally. Dishwasher / disposal / microwave circuits follow manufacturer instructions.

There is no NEC limit on the number of receptacles or lights per dwelling branch circuit; electricians use their own rules of thumb and some jurisdictions add local limits. The receptacle and kitchen rules are detailed in NEC 210.52 receptacle spacing and GFCI and AFCI requirements by room.

Service size and the 200 A panel

The NEC minimum for a one-family dwelling is a 100 A service (230.79(C)). An all-electric house with a range, dryer, water heater, heat pump and an EV charger will usually need 200 A, which the load calculation confirms: the optional method (220.82) takes 3 VA/ft², 1,500 VA per small-appliance and laundry circuit and the nameplate of every fastened appliance, counts 10,000 VA at 100 % and the rest at 40 %, then adds the heat pump. See residential load calculation (NEC 220).

  • A 200 A load center with 40 spaces is typical; 120 V circuits use one space, 240 V circuits a two-pole breaker across both lines.
  • Leave spare spaces for later (practice is around 20 %), for example a second EV charger or a battery.
  • Outdoor emergency disconnect (230.85) and a surge protective device at the service (230.67).
  • Working space 30 in wide, 36 in deep, 6.5 ft high in front of the panel; not in a bathroom or a clothes closet. A garage or utility room wall is the usual spot.
  • Neutral and ground are bonded only at the service; any subpanel keeps them separate.
  • Every circuit is identified in the panel directory (408.4): see the panel schedule template.

Smoke and CO alarms

The IRC requires smoke alarms in each sleeping room, outside each sleeping area in the immediate vicinity of the bedrooms and on each story, including basements. They are powered from the building wiring with battery backup, with no switch other than the breaker, and interconnected so that one sounding sets off all (R314). A house with fuel-burning appliances or an attached garage also needs CO alarms outside each sleeping area and on each story (R315); combination smoke / CO alarms are allowed. In the example house, that means three bedroom alarms plus a combination alarm in the hallway.

Permit and inspections for a new house

On a new house, the electrical work is usually done by a licensed electrical contractor who pulls the electrical permit. Many jurisdictions allow a homeowner to pull a permit for their own single-family home; rules vary by state and city. The plan is reviewed, then inspected at rough-in (boxes, cable, grounding, before insulation) and at final (devices, GFCI / AFCI, panel directory, alarms). The utility energizes the service after the inspection. The drawing itself is covered in how to draw an electrical plan for a permit.

Drawing the house in Circuia

Draw the rooms on the grid in feet and inches and label them (kitchen, bedroom, bathroom, garage…). Equip the rooms places receptacles by the 210.52 rules (6 ft wall rule, 24 in countertop rule, 3 ft from basins, hallways of 10 ft or more) and a switched lighting outlet in each room. Automatic wiring builds the circuits: 14 AWG / 15 A lighting, 12 AWG / 20 A receptacles, the two 20 A small-appliance circuits, a 20 A bathroom circuit and 240 V two-pole circuits for the range, water heater and EV charger. The check flags missing GFCI or AFCI protection, wire sizes that don't match breakers, missing small-appliance circuits and more.

Export on Letter paper: floor plan with symbols, panel schedule, single-line diagram and materials list, and send a share link to your client or builder. Drawing and checking are free; the Project Pass ($45 one-off, plus sales tax) unlocks the PDFs and materials list for one home.

Draw your house in the editor, free, in your browser.

Common mistakes

  • Counting only furniture walls: every wall space 2 ft or wider counts for the 6 ft rule.
  • Putting lighting or receptacles from other rooms on a small-appliance circuit (it serves kitchen, pantry and dining receptacles only; the refrigerator may instead have its own 15 A or larger circuit).
  • Forgetting the receptacle in the hallway or the outdoor receptacle at the back of the house.
  • Undersizing the panel: no spare spaces left for an EV charger or a heat pump later.
  • Smoke alarms in bedrooms only, without the one in the hallway and on each story, or not interconnected.

Frequently asked questions

What size electrical service does a new house need?

The NEC minimum for a one-family dwelling is 100 A (230.79(C)). 200 A is the common choice for a new house, especially when cooking, water heating and heating are electric and an EV charger is planned. The actual size comes from the load calculation (NEC 220.82 optional method for a one-family dwelling), which your permit office may ask to see.

How many circuits does a 3-bedroom house need?

It depends on the floor area and appliances. For 1,800 ft², general lighting at 3 VA/ft² gives 5,400 VA, so at least 3 general 15 A circuits, plus two 20 A small-appliance circuits, a 20 A laundry, bathroom and garage circuit, and dedicated circuits for the range, dryer, water heater, dishwasher, HVAC and EV charger. Your load calculation and panel size follow from that list.

Which rooms need AFCI and which need GFCI?

Under NEC 2023, AFCI protects 120 V 15 and 20 A circuits supplying kitchens, family, living and dining rooms, bedrooms, closets, hallways, laundry areas and similar rooms. GFCI protects receptacles in bathrooms, kitchens, garages, outdoors, laundry areas, basements and within 6 ft of sinks, tubs and showers. Kitchens and laundry need both, often with a dual-function breaker.

Where do smoke alarms go in a new house?

In each bedroom, outside each sleeping area near the bedrooms, and on each story including the basement (IRC R314). They are hard-wired with battery backup and interconnected. If the house has fuel-burning appliances or an attached garage, CO alarms are also required outside each sleeping area (IRC R315); combination smoke / CO alarms are allowed.

Can Circuia design the whole house electrical plan?

It places receptacles and switched lighting by the NEC 210.52 rules, builds the branch circuits, checks GFCI, AFCI and wire sizing, and exports the plan, panel schedule, single-line diagram and materials list. Its US rules pack has not been reviewed by a US master electrician, so a licensed electrician, the permit office and the inspections still have the final word.

Design aid

Design the installation with this country's rules

Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.

Open a free sample plan with these rules

Written by

Circuia team

Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.