Residential load calculation (NEC 220) explained, with a worked example

A residential load calculation turns the floor area and the appliances of a house into a demand in volt-amperes, then divides it by 240 V to size the service. Under NEC 2023 Article 220 you count 3 VA per ft² of general lighting, 1,500 VA per small-appliance and laundry circuit, the appliances at their nameplate, and apply demand factors. A 2,000 ft² house with a range, a dryer, an EV charger and central air lands around 156 A with the standard method.

Updated on Last checked NEC (NFPA 70) 2023

Key facts

  • 01General lighting: 3 VA/ft² of floor area (220.41), plus 1,500 VA for each small-appliance circuit (at least 2) and for the laundry circuit.
  • 02Standard method demand factors (Table 220.45): first 3,000 VA at 100 %, 3,001 to 120,000 VA at 35 %, the remainder at 25 %.
  • 03Range: 8 kW for one range up to 12 kW (Table 220.55). Dryer: at least 5,000 VA (220.54). EVSE: at least 7,200 VA or the nameplate, whichever is larger (220.57).
  • 04Optional method (220.82): first 10 kVA at 100 %, the rest of the general load at 40 %, plus heating or air conditioning at the 220.82(C) percentages.
  • 05A one-family dwelling needs a service of at least 100 A (230.79(C)); 200 A is the usual size for a new house.
  • 06The 2026 NEC moves Article 220 to Article 120 (120.41, 120.57, 120.82, 120.83): same method, new section numbers.

What a load calculation is for

The load calculation answers one question: how large must the service and the feeder be? It is not the sum of every breaker in the panel. Nobody runs the range, the dryer, the water heater, the EV charger and every receptacle at full power at the same time, so the NEC applies demand factors that reflect real diversity in a home. The result, in volt-amperes, divided by 240 V gives the minimum ampacity of the service conductors and the main breaker.

Most AHJs ask for a load calculation with the permit for a new house, a service upgrade or a large addition such as an EV charger or a heat pump. Many publish their own worksheet. The NEC offers two methods for a one-family dwelling: the standard method (220.40 and following) and the optional method (220.82 for new dwellings, 220.83 for existing ones). Both are legitimate; the optional method usually gives a smaller result for all-electric homes.

The standard method, step by step

  1. General lighting and receptacles: 3 VA per ft² of floor area, measured from the outside dimensions, excluding open porches and unfinished spaces (220.41). This load covers the general-purpose receptacles too.
  2. Small-appliance and laundry circuits: add 1,500 VA for each small-appliance circuit (at least 2) and 1,500 VA for the laundry circuit.
  3. Apply Table 220.45 to the sum of steps 1 and 2: the first 3,000 VA at 100 %, the next part up to 120,000 VA at 35 %, anything above at 25 %.
  4. Fastened-in-place appliances (water heater, dishwasher, disposal…): their nameplate rating, at 75 % when there are four or more (220.53). Cooking equipment, dryers, space heating, air conditioning and EVSE are not part of this group.
  5. Clothes dryer: 5,000 VA or the nameplate, whichever is larger (220.54).
  6. Range and cooking appliances: Table 220.55. One range rated 12 kW or less counts as 8 kW. For larger ranges, several cooking units or separate ovens and cooktops, read the table and its notes in the code text.
  7. EV charging equipment: 7,200 VA or the nameplate, whichever is larger (220.57).
  8. Heating and air conditioning: count only the larger of the two, since they do not run together (220.60).
  9. Add everything and divide by 240 V: that is the minimum service ampacity. Round up to a standard size (100, 125, 150, 200, 225 A…).

Motors (the largest motor at 125 %), fixed electric space heating and heat pumps with supplementary heat have their own rules that are not detailed here. If your house has them, check the code text or your AHJ's worksheet.

Worked example: a 2,000 ft² house

Assume a 2,000 ft² one-family house with a 12 kW electric range, an electric dryer, a 4,500 W water heater, a dishwasher, a disposal, a built-in microwave, a 32 A Level 2 EV charger on a 40 A breaker and 5,000 VA of central air conditioning with a gas furnace. Nameplate values are typical figures chosen for the example; use the real ones on your appliances.

Standard method, 2,000 ft² house (NEC 2023 Article 220)
LoadCalculationDemand (VA)
General lighting2,000 ft² × 3 VA6,000
Small-appliance circuits2 × 1,500 VA3,000
Laundry circuit1 × 1,500 VA1,500
Subtotal before demand factor10,500
After Table 220.453,000 at 100 % + 7,500 at 35 %5,625
Fastened appliances (4)Water heater 4,500 + Dishwasher 1,200 + Garbage disposal 900 + Built-in microwave 1,500 = 8,100 × 75 %6,075
Clothes dryer5,000 VA minimum (220.54)5,000
Range 12 kWTable 220.55, one range ≤ 12 kW8,000
EV charger32 A × 240 V (above the 7,200 VA minimum)7,680
Air conditioningLarger of heating and cooling (220.60)5,000
Total37,380
Service current37,380 ÷ 240 V155.8 A → 200 A service
Some designers count a built-in microwave with the cooking equipment of Table 220.55 rather than with fastened appliances; check how your AHJ wants it. Motor and heating details are simplified.

The result is just over 150 A, so the next standard size, 200 A, is required. With a 200 A service, the service-entrance conductors for a dwelling are commonly 2/0 copper or 4/0 aluminum under the 83 % rule of 310.12; confirm against the table in the adopted code.

The optional method (220.82) on the same house

The optional method is open to a one-family dwelling supplied at 120/240 V, 3-wire, with a service of 100 A or more. Instead of separate demand factors for each appliance, it adds everything into one "general load" and applies a single factor, then adds heating or cooling separately.

Optional method (220.82), same 2,000 ft² house
StepCalculationVA
Lighting, small-appliance and laundry6,000 + 3,000 + 1,50010,500
Appliances fastened in place, at nameplatewater heater, dishwasher, disposal, microwave 8,100 + dryer 5,000 + range 12,000 + EVSE 7,68032,780
General load43,280
Demand on the general load10,000 at 100 % + 33,280 at 40 %23,312
Air conditioning (220.82(C))100 % of the A/C load5,000
Total28,312
Service current28,312 ÷ 240 V118.0 A → 125 A minimum
How EVSE is treated under 220.82 (here: at nameplate inside the general load) and under the 2026 section 120.82 is reported differently by secondary sources — check the code text and your AHJ.

The heating and cooling percentages of 220.82(C) are: 100 % of the air-conditioning or heat-pump compressor load; 100 % of a heat pump plus 65 % of its supplementary electric heat; 65 % of central electric space heating; 65 % of fewer than four separately controlled space heaters, 40 % of four or more. Take the largest that applies.

Here the optional method gives a smaller minimum than the standard method. In practice most new houses still get 200 A to leave room for a heat pump or a second EV, but the optional method is often what makes an EV charger fit on an existing 100 or 150 A service (220.83 for existing dwellings).

NEC 2026: Article 220 becomes Article 120

The 2026 edition reorganizes the code and relocates the load calculations to Article 120: 220.41 becomes 120.41, 220.57 becomes 120.57, 220.82 becomes 120.82 and 220.83 becomes 120.83. The method described on this page is unchanged in substance according to the summaries we read. If your jurisdiction is on the 2026 edition (Massachusetts, Minnesota, Texas, Washington and a few cities so far), quote the 120.x numbers on your permit documents.

What Circuia does, and does not do, for the load calculation

Circuia does not compute a full Article 220 service calculation today. What it does: auto-wire builds the branch circuits of your plan, two-pole 240 V circuits for the range, dryer, water heater and EV charger, and the panel schedule lists every circuit with its breaker, poles, wire size and room. That schedule is the load list you start from. The compliance check also warns when lines L1 and L2 differ by more than about 20 A of estimated load. The service size itself is calculated with the method on this page, by you or your electrician, on the AHJ's form.

Open the editor set up for the United States — free to start in your browser. Plans: a one-off Project Pass at $45 or Pro at $55 per month, plus sales tax.

Common mistakes

  • Adding up every breaker rating and calling it the load: breakers are sized for each circuit, not for the whole house at once.
  • Forgetting the 1,500 VA per small-appliance and laundry circuit on top of the 3 VA/ft².
  • Counting both the electric heat and the air conditioning in the standard method: only the larger one counts (220.60).
  • Entering the dryer below 5,000 VA or the EV charger below 7,200 VA.
  • Using the optional method for something other than a one-family dwelling at 120/240 V with a 100 A or larger service.
  • Measuring floor area from the inside walls or including open porches and unfinished spaces.

Frequently asked questions

How many VA per square foot for a residential load calculation?

The NEC counts 3 volt-amperes per square foot of floor area for general lighting and general-purpose receptacles in a dwelling (220.41 in the 2023 edition, 120.41 in 2026). The area is measured from the outside dimensions and excludes open porches and unfinished spaces. Small-appliance and laundry circuits are added separately at 1,500 VA each.

What size service does a 2,000 square foot house need?

It depends on the appliances, not only the area. In the worked example on this page, a 2,000 ft² house with an electric range, an electric dryer, a water heater, an EV charger and central air gives about 37,380 VA with the standard method, or 156 A at 240 V, so a 200 A service. The same house with gas cooking and no EV charger comes out near 90 A, close to the 100 A minimum.

What is the difference between the standard and the optional method?

The standard method applies separate demand factors to each group of loads: lighting and small-appliance circuits through Table 220.45, fastened appliances at 75 % when there are four or more, ranges through Table 220.55, and so on. The optional method of 220.82 lumps the general load together, counts the first 10 kVA at 100 % and the rest at 40 %, then adds heating or cooling. It usually gives a lower result.

How is an EV charger counted in a load calculation?

Under 220.57 of the 2023 NEC, EV charging equipment counts at 7,200 VA or its nameplate rating, whichever is larger. A 32 A Level 2 charger at 240 V is 7,680 VA. Its branch circuit is sized separately: the breaker must be at least 125 % of the charger current, so 40 A for a 32 A charger. How the optional method treats EVSE is worth confirming in the code text.

Did the 2026 NEC change the load calculation?

The 2026 edition relocated the load calculation rules from Article 220 to Article 120, so 220.82 becomes 120.82, 220.57 becomes 120.57, and so on. According to the summaries of the changes, the method itself is substantially the same. Use the section numbers of the edition your jurisdiction has adopted on your permit documents, and check your AHJ's worksheet.

Does Circuia calculate the service size for me?

No. Circuia builds the branch circuits, checks them against its US rules pack and produces a panel schedule listing every circuit, which is the list of loads you need to start a calculation. It does not compute the Article 220 service calculation. Use the method on this page or the worksheet of your AHJ, and have a licensed electrician confirm the service size.

Design aid

Design the installation with this country's rules

Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.

Open a free sample plan with these rules

Written by

Circuia team

Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.

Published · updated