Guide · United States · NEC 210.8 / 210.12
GFCI vs AFCI requirements by room (NEC 2023)
A GFCI protects people from shock by tripping on a few milliamps of current leaking to ground; an AFCI protects the building from fire by detecting arcing in the wiring. Under NEC 2023, GFCI follows water and damp locations (210.8): kitchens, bathrooms, garages, outdoors, basements, laundry areas, anything within 6 ft of a sink. AFCI follows living spaces (210.12): bedrooms, living rooms, kitchens, hallways, closets, laundry. Kitchens and laundry areas need both.
Updated on Last checked NEC (NFPA 70) 2023
Key facts
- 01GFCI (UL 943, Class A) trips at roughly 4–6 mA of ground fault current: it protects people. AFCI (combination type, UL 1699) detects dangerous arcs: it protects against fires.
- 02GFCI (210.8(A)): all 125–250 V receptacles in bathrooms, kitchens (all receptacles since 2023), garages, outdoors, crawl spaces, basements, laundry areas and within 6 ft of a sink, tub or shower.
- 03AFCI (210.12(A)): all 120 V, 10, 15 and 20 A branch circuits supplying kitchens, family, dining and living rooms, bedrooms, closets, hallways, laundry areas and similar rooms (10 A added in 2023).
- 04Kitchens and laundry areas need both, usually through a dual-function AFCI/GFCI breaker.
- 05NEC 2023 added GFCI for ranges, wall ovens, cooktops, clothes dryers and microwave ovens (210.8(D) / 422.5(A)) — some jurisdictions amended this out, so check locally.
GFCI vs AFCI: what each device actually does
The two acronyms look alike but protect against different hazards. A ground-fault circuit interrupter (GFCI) compares the current going out on the hot conductor with the current coming back on the neutral. If a few milliamps are missing, they are flowing somewhere else, possibly through a person standing on a wet floor, and the device opens the circuit in a fraction of a second. Residential GFCIs are Class A devices listed to UL 943 and trip at roughly 4 to 6 mA.
An arc-fault circuit interrupter (AFCI) watches the waveform of the current for the signature of an electrical arc: a nail through a cable, a loose connection in a backstabbed receptacle, a crushed extension cord behind a bed. Those arcs can start a fire long before a standard breaker would trip on overcurrent. The NEC requires the combination type (UL 1699), which detects both series and parallel arcs.
| Device | Protects against | Where it sits | Typical use |
|---|---|---|---|
| GFCI breaker | Shock (ground fault) | Panel | Whole circuit: garage, outdoors, bathrooms, basement |
| GFCI receptacle | Shock (ground fault) | First box of the circuit | Protects itself and every receptacle wired to its LOAD terminals |
| Combination AFCI breaker | Fire (arc fault) | Panel | Bedrooms, living areas, hallways, closets |
| Dual-function AFCI/GFCI breaker | Both | Panel | Kitchen small-appliance circuits, laundry |
| Outlet branch-circuit AFCI (OBC-AFCI) | Fire (arc fault) | First outlet of the circuit | Extending or modifying an existing circuit (210.12(D)) |
GFCI and AFCI requirements room by room (NEC 2023)
The table below maps each room of a one-family dwelling to sections 210.8(A) (GFCI on 125–250 V receptacles) and 210.12(A) (AFCI on 120 V, 10, 15 and 20 A branch circuits). "Sink rule" means receptacles within 6 ft of the top inside edge of a sink bowl, or of a bathtub or shower, need GFCI wherever they are (210.8(A)(7) to (9)).
| Room | GFCI (210.8) | AFCI (210.12) | Notes |
|---|---|---|---|
| Kitchen | Yes, all receptacles (2023; before 2023 only countertop receptacles) | Yes | 2 × 20 A small-appliance circuits, usually dual-function breakers |
| Bathroom | Yes, all receptacles | Not listed in 210.12(A) — check local amendments | 20 A bathroom receptacle circuit (210.11(C)(3)) |
| Bedroom (and its closets) | Sink rule only | Yes | Tamper-resistant receptacles; smoke alarm in the room |
| Living, family, dining room, den | Sink rule only (e.g. wet bar) | Yes | Dining receptacles are on the small-appliance circuits |
| Hallway, foyer | No | Yes | A hallway of 10 ft or more needs a receptacle |
| Closet | No | Yes | No panel in a clothes closet (240.24(D)) |
| Laundry area | Yes | Yes | Dedicated 20 A laundry circuit (210.11(C)(2)) |
| Garage, accessory building | Yes, all 125–250 V receptacles | No | Dedicated 20 A garage circuit (210.11(C)(4)) |
| Basement | Yes | Unfinished: no. Finished: commonly treated as habitable — check with your inspector | At least one receptacle per unfinished portion |
| Crawl space | Yes | No | Unfinished space, like an unfinished basement |
| Outdoors (deck, porch, balcony) | Yes, receptacles; outdoor outlets up to 50 A (210.8(F)) | No | Weather-resistant receptacles and in-use covers in wet locations (406.9(B)) |
| Toilet room without a basin | Sink rule only | Commonly yes as a "similar room" — check locally | Not a "bathroom" in NEC terms |
| Within 6 ft of any sink, tub or shower | Yes | Per the room | Measured from the top inside edge of the bowl; includes wet bars |
Dishwashers, ranges, dryers: the appliance GFCI rules
GFCI is not only about receptacles in a room. Section 210.8(D) points to 422.5(A), which lists appliances that need GFCI protection whether they are plugged in or hard-wired. The dishwasher has been on that list since before 2020, so a dishwasher circuit needs GFCI even when the receptacle sits under the sink cabinet.
The 2023 edition added ranges, wall-mounted ovens, counter-mounted cooking units (cooktops), clothes dryers and microwave ovens. The exact voltage and current limits of that list are worth reading in the adopted code text. This change drew complaints about nuisance tripping of older appliances, and several AHJs amended ranges and dryers out when adopting NEC 2023. Before buying a 40 A two-pole GFCI breaker for a range, ask your permit office whether the requirement applies where you build.
GFCI breaker or GFCI receptacle? AFCI breaker or OBC-AFCI?
The code requires the protection, not a particular device. In new construction the choice usually comes down to cost, convenience and how many locations a circuit serves.
- GFCI receptacle at the first box: cheaper, and a single device protects every receptacle downstream on its LOAD terminals. Label the downstream receptacles "GFCI protected". It must stay readily accessible.
- GFCI breaker: one reset point in the panel, nothing to hunt for behind furniture. Required where the outlet is not a receptacle (a hard-wired dishwasher or range) unless the appliance has its own protection.
- Dual-function AFCI/GFCI breaker: the usual answer where both are required, i.e. kitchen small-appliance circuits and laundry circuits. Without it you combine an AFCI breaker with GFCI receptacles.
- OBC-AFCI receptacle: allowed by 210.12(D) when an existing circuit is extended or modified in a remodel, so you do not have to change the breaker in an old panel that has no compatible AFCI model.
- Tamper-resistant receptacles are required everywhere in a dwelling (406.12) regardless of GFCI or AFCI; outdoors they must also be weather-resistant (406.9).
Whatever you choose, test each device with its test button at the final inspection: the inspector will usually do it anyway.
What changes with the 2026 NEC
The 2026 NEC was issued in August 2025 and is already in force in a handful of states. For GFCI and AFCI in dwellings the changes are modest:
- Outdoor outlets (210.8(F)) go from 50 A to 60 A. The exception for HVAC equipment runs until 1 September 2026 (tied to UL 943 Supplement SB); it does not apply to outlets that are not readily accessible or to lighting outlets. Texas adopted the 2026 NEC with a local exception on this rule.
- OBC-AFCI devices may be installed at the first receptacle or switch when a circuit is extended (210.12).
- The load calculations of Article 220 move to Article 120 — not a GFCI change, but every section number you look up shifts.
AFCI in bathrooms, toilet rooms and finished basements remains a frequent local question under both editions. The spec Circuia is built on lists it as open: if your AHJ requires it, follow your AHJ.
How Circuia checks GFCI and AFCI on your plan
Draw the rooms, place the receptacles and fixtures, and the compliance check flags every circuit missing GFCI (210.8) or AFCI (210.12) protection for the rooms it serves, together with conductor size against breaker (240.4(D)), the 2 small-appliance circuits of 20 A and the 20 A bathroom circuit. Tamper-resistant receptacles and smoke alarms appear as reminders. Auto-wire builds the circuits for you, and the PDF on Letter paper includes the panel schedule with a GFCI/AFCI column.
Open the editor set up for the United States — free to start in your browser. Plans: a one-off Project Pass at $45 or Pro at $55 per month, plus sales tax.
Common mistakes
- Protecting only the countertop receptacles in a kitchen: since NEC 2023 all kitchen receptacles need GFCI, including the refrigerator receptacle.
- Hiding the only GFCI receptacle of a circuit behind an appliance or inside a cabinet: GFCI devices must be readily accessible.
- Forgetting the dishwasher: it needs GFCI under 422.5(A) even when hard-wired or plugged in under the sink.
- Putting a plain AFCI breaker on a kitchen circuit and no GFCI anywhere downstream: kitchens and laundry areas need both.
- Assuming the 2023 range and dryer GFCI rule applies everywhere, or that it never does: check your AHJ's amendments.
- Treating a basement as finished or unfinished without asking the inspector which AFCI rule they apply.
Frequently asked questions
What is the difference between a GFCI and an AFCI?
Do kitchen receptacles need GFCI and AFCI?
Do bathrooms need AFCI protection?
Does a garage need AFCI?
Do ranges and dryers need GFCI protection?
Can one GFCI receptacle protect several outlets?
Does Circuia replace an electrician or an inspection?
Design aid
Design the installation with this country's rules
Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.
Written by
Circuia team
Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.
Published · updated
Sources
Sources used for this page, official texts first:
- NFPA 70, National Electrical Code 2023 — free access
- NFPA 70, National Electrical Code 2026 — free access
- UL Code Authority — 2026 NEC dates and 210.8(F)
- City of Saint Paul DSI — AFCI protection bulletin
- City of Champlin, MN — 2026 National Electrical Code FAQ
- IAEI Magazine — Powering forward: major changes in the 2023 NEC
- EC&M — What's cooking in the kitchen for the 2023 NEC
Related pages
- GuideNEC 2023 for homes: the residential rules that matter (National Electrical Code)NEC 2023 for one- and two-family homes: required circuits, receptacle spacing, GFCI/AFCI, wire sizes, panel and permits. Plus a free NEC compliance check.
- GuideKitchen countertop receptacle requirements (NEC 2023): spacing, islands, circuits and GFCINEC 2023 kitchen rules: the 24 in countertop receptacle rule, islands and peninsulas, two 20 A small-appliance circuits, GFCI on every kitchen receptacle.
- GuideNEC receptacle spacing rules (210.52): the 6 ft / 12 ft rule, room by roomHow NEC 210.52 spaces receptacles in a house: the 6 ft / 12 ft rule, what counts as wall space, hallways, bathrooms, garages and a worked bedroom example.
- GuidePanel schedule template for a house (NEC 408.4 circuit directory)A panel schedule template for a house: the columns to fill, a filled 200 A example with L1/L2 positions, NEC 408.4 labeling rules and 110.26 working space.
- CircuiaPricing: free, Project Pass €29, Pro €49/monthCircuia plans: Free to explore, Project Pass at €29 incl. VAT for a homeowner project, Pro at €49 excl. VAT/month and Team at €129 excl. VAT/month for electricians. 14-day trial.