Guide · United States · NEC 210.8 / 210.12

GFCI vs AFCI requirements by room (NEC 2023)

A GFCI protects people from shock by tripping on a few milliamps of current leaking to ground; an AFCI protects the building from fire by detecting arcing in the wiring. Under NEC 2023, GFCI follows water and damp locations (210.8): kitchens, bathrooms, garages, outdoors, basements, laundry areas, anything within 6 ft of a sink. AFCI follows living spaces (210.12): bedrooms, living rooms, kitchens, hallways, closets, laundry. Kitchens and laundry areas need both.

Updated on Last checked NEC (NFPA 70) 2023

Key facts

  • 01GFCI (UL 943, Class A) trips at roughly 4–6 mA of ground fault current: it protects people. AFCI (combination type, UL 1699) detects dangerous arcs: it protects against fires.
  • 02GFCI (210.8(A)): all 125–250 V receptacles in bathrooms, kitchens (all receptacles since 2023), garages, outdoors, crawl spaces, basements, laundry areas and within 6 ft of a sink, tub or shower.
  • 03AFCI (210.12(A)): all 120 V, 10, 15 and 20 A branch circuits supplying kitchens, family, dining and living rooms, bedrooms, closets, hallways, laundry areas and similar rooms (10 A added in 2023).
  • 04Kitchens and laundry areas need both, usually through a dual-function AFCI/GFCI breaker.
  • 05NEC 2023 added GFCI for ranges, wall ovens, cooktops, clothes dryers and microwave ovens (210.8(D) / 422.5(A)) — some jurisdictions amended this out, so check locally.

GFCI vs AFCI: what each device actually does

The two acronyms look alike but protect against different hazards. A ground-fault circuit interrupter (GFCI) compares the current going out on the hot conductor with the current coming back on the neutral. If a few milliamps are missing, they are flowing somewhere else, possibly through a person standing on a wet floor, and the device opens the circuit in a fraction of a second. Residential GFCIs are Class A devices listed to UL 943 and trip at roughly 4 to 6 mA.

An arc-fault circuit interrupter (AFCI) watches the waveform of the current for the signature of an electrical arc: a nail through a cable, a loose connection in a backstabbed receptacle, a crushed extension cord behind a bed. Those arcs can start a fire long before a standard breaker would trip on overcurrent. The NEC requires the combination type (UL 1699), which detects both series and parallel arcs.

The protective devices you will meet in a US panel
DeviceProtects againstWhere it sitsTypical use
GFCI breakerShock (ground fault)PanelWhole circuit: garage, outdoors, bathrooms, basement
GFCI receptacleShock (ground fault)First box of the circuitProtects itself and every receptacle wired to its LOAD terminals
Combination AFCI breakerFire (arc fault)PanelBedrooms, living areas, hallways, closets
Dual-function AFCI/GFCI breakerBothPanelKitchen small-appliance circuits, laundry
Outlet branch-circuit AFCI (OBC-AFCI)Fire (arc fault)First outlet of the circuitExtending or modifying an existing circuit (210.12(D))
GFCI devices must be readily accessible (210.8): a GFCI receptacle hidden behind a refrigerator or inside a cabinet does not count. Sources: St Paul DSI AFCI bulletin, IAEI magazine (2023 changes).

GFCI and AFCI requirements room by room (NEC 2023)

The table below maps each room of a one-family dwelling to sections 210.8(A) (GFCI on 125–250 V receptacles) and 210.12(A) (AFCI on 120 V, 10, 15 and 20 A branch circuits). "Sink rule" means receptacles within 6 ft of the top inside edge of a sink bowl, or of a bathtub or shower, need GFCI wherever they are (210.8(A)(7) to (9)).

GFCI and AFCI by room, one-family dwelling, NEC 2023
RoomGFCI (210.8)AFCI (210.12)Notes
KitchenYes, all receptacles (2023; before 2023 only countertop receptacles)Yes2 × 20 A small-appliance circuits, usually dual-function breakers
BathroomYes, all receptaclesNot listed in 210.12(A) — check local amendments20 A bathroom receptacle circuit (210.11(C)(3))
Bedroom (and its closets)Sink rule onlyYesTamper-resistant receptacles; smoke alarm in the room
Living, family, dining room, denSink rule only (e.g. wet bar)YesDining receptacles are on the small-appliance circuits
Hallway, foyerNoYesA hallway of 10 ft or more needs a receptacle
ClosetNoYesNo panel in a clothes closet (240.24(D))
Laundry areaYesYesDedicated 20 A laundry circuit (210.11(C)(2))
Garage, accessory buildingYes, all 125–250 V receptaclesNoDedicated 20 A garage circuit (210.11(C)(4))
BasementYesUnfinished: no. Finished: commonly treated as habitable — check with your inspectorAt least one receptacle per unfinished portion
Crawl spaceYesNoUnfinished space, like an unfinished basement
Outdoors (deck, porch, balcony)Yes, receptacles; outdoor outlets up to 50 A (210.8(F))NoWeather-resistant receptacles and in-use covers in wet locations (406.9(B))
Toilet room without a basinSink rule onlyCommonly yes as a "similar room" — check locallyNot a "bathroom" in NEC terms
Within 6 ft of any sink, tub or showerYesPer the roomMeasured from the top inside edge of the bowl; includes wet bars
Sources: NFPA 70 (2023) free access, IAEI magazine, St Paul DSI bulletins. Item numbering inside 210.8(A) changed between editions; check the code text adopted by your AHJ.

Dishwashers, ranges, dryers: the appliance GFCI rules

GFCI is not only about receptacles in a room. Section 210.8(D) points to 422.5(A), which lists appliances that need GFCI protection whether they are plugged in or hard-wired. The dishwasher has been on that list since before 2020, so a dishwasher circuit needs GFCI even when the receptacle sits under the sink cabinet.

The 2023 edition added ranges, wall-mounted ovens, counter-mounted cooking units (cooktops), clothes dryers and microwave ovens. The exact voltage and current limits of that list are worth reading in the adopted code text. This change drew complaints about nuisance tripping of older appliances, and several AHJs amended ranges and dryers out when adopting NEC 2023. Before buying a 40 A two-pole GFCI breaker for a range, ask your permit office whether the requirement applies where you build.

GFCI breaker or GFCI receptacle? AFCI breaker or OBC-AFCI?

The code requires the protection, not a particular device. In new construction the choice usually comes down to cost, convenience and how many locations a circuit serves.

  • GFCI receptacle at the first box: cheaper, and a single device protects every receptacle downstream on its LOAD terminals. Label the downstream receptacles "GFCI protected". It must stay readily accessible.
  • GFCI breaker: one reset point in the panel, nothing to hunt for behind furniture. Required where the outlet is not a receptacle (a hard-wired dishwasher or range) unless the appliance has its own protection.
  • Dual-function AFCI/GFCI breaker: the usual answer where both are required, i.e. kitchen small-appliance circuits and laundry circuits. Without it you combine an AFCI breaker with GFCI receptacles.
  • OBC-AFCI receptacle: allowed by 210.12(D) when an existing circuit is extended or modified in a remodel, so you do not have to change the breaker in an old panel that has no compatible AFCI model.
  • Tamper-resistant receptacles are required everywhere in a dwelling (406.12) regardless of GFCI or AFCI; outdoors they must also be weather-resistant (406.9).

Whatever you choose, test each device with its test button at the final inspection: the inspector will usually do it anyway.

What changes with the 2026 NEC

The 2026 NEC was issued in August 2025 and is already in force in a handful of states. For GFCI and AFCI in dwellings the changes are modest:

  • Outdoor outlets (210.8(F)) go from 50 A to 60 A. The exception for HVAC equipment runs until 1 September 2026 (tied to UL 943 Supplement SB); it does not apply to outlets that are not readily accessible or to lighting outlets. Texas adopted the 2026 NEC with a local exception on this rule.
  • OBC-AFCI devices may be installed at the first receptacle or switch when a circuit is extended (210.12).
  • The load calculations of Article 220 move to Article 120 — not a GFCI change, but every section number you look up shifts.

AFCI in bathrooms, toilet rooms and finished basements remains a frequent local question under both editions. The spec Circuia is built on lists it as open: if your AHJ requires it, follow your AHJ.

How Circuia checks GFCI and AFCI on your plan

Draw the rooms, place the receptacles and fixtures, and the compliance check flags every circuit missing GFCI (210.8) or AFCI (210.12) protection for the rooms it serves, together with conductor size against breaker (240.4(D)), the 2 small-appliance circuits of 20 A and the 20 A bathroom circuit. Tamper-resistant receptacles and smoke alarms appear as reminders. Auto-wire builds the circuits for you, and the PDF on Letter paper includes the panel schedule with a GFCI/AFCI column.

Open the editor set up for the United States — free to start in your browser. Plans: a one-off Project Pass at $45 or Pro at $55 per month, plus sales tax.

Common mistakes

  • Protecting only the countertop receptacles in a kitchen: since NEC 2023 all kitchen receptacles need GFCI, including the refrigerator receptacle.
  • Hiding the only GFCI receptacle of a circuit behind an appliance or inside a cabinet: GFCI devices must be readily accessible.
  • Forgetting the dishwasher: it needs GFCI under 422.5(A) even when hard-wired or plugged in under the sink.
  • Putting a plain AFCI breaker on a kitchen circuit and no GFCI anywhere downstream: kitchens and laundry areas need both.
  • Assuming the 2023 range and dryer GFCI rule applies everywhere, or that it never does: check your AHJ's amendments.
  • Treating a basement as finished or unfinished without asking the inspector which AFCI rule they apply.

Frequently asked questions

What is the difference between a GFCI and an AFCI?

A GFCI (ground-fault circuit interrupter) trips when a few milliamps of current leak to ground, roughly 4 to 6 mA for the Class A devices used in homes, which protects people from electric shock. An AFCI (arc-fault circuit interrupter) detects the current signature of arcing in wiring or cords, which protects the building from fire. The NEC requires GFCI in wet and damp locations (210.8) and AFCI in living spaces (210.12); some rooms need both.

Do kitchen receptacles need GFCI and AFCI?

Yes, under NEC 2023 both apply. GFCI now covers all 125–250 V receptacles in a kitchen, not only those serving the countertop, and AFCI covers the 120 V 15 and 20 A circuits supplying the kitchen. The 2 required 20 A small-appliance circuits are therefore usually protected by dual-function AFCI/GFCI breakers. Check whether your jurisdiction has amended these rules.

Do bathrooms need AFCI protection?

Bathrooms are not in the AFCI list of 210.12(A) in the editions summarized here, so the national rule is GFCI on all bathroom receptacles plus a 20 A receptacle circuit. Some jurisdictions add AFCI through local amendments, and the question is still debated for the 2026 edition, so check with your inspector before you buy breakers.

Does a garage need AFCI?

Not under 210.12(A): garages are not on the list of living spaces that need arc-fault protection. Garage receptacles do need GFCI protection (all 125–250 V receptacles), and an attached garage needs at least one dedicated 20 A receptacle circuit under 210.11(C)(4). If the garage has been converted into a habitable room, it is treated like the room it has become.

Do ranges and dryers need GFCI protection?

The 2023 NEC added ranges, wall ovens, cooktops, clothes dryers and microwave ovens to the appliances that need GFCI protection (210.8(D) and 422.5(A)). Several AHJs amended ranges and dryers out when they adopted the 2023 edition because of nuisance tripping concerns. Ask your permit office which version applies to your project before buying two-pole GFCI breakers.

Can one GFCI receptacle protect several outlets?

Yes. A GFCI receptacle protects every receptacle wired to its LOAD terminals, so one device at the first box can cover a whole bathroom or garage circuit. The protected receptacles should be marked "GFCI protected", and the GFCI itself must stay readily accessible, not behind a refrigerator or inside a cabinet. A GFCI breaker in the panel does the same job for the entire circuit.

Does Circuia replace an electrician or an inspection?

No. Circuia checks a plan against its US rules pack, built from public sources without review by a US master electrician. It flags missing GFCI and AFCI protection and other common errors, and produces the plan and panel schedule. A licensed electrician (or a homeowner permit where allowed) and the AHJ's inspections remain required.

Design aid

Design the installation with this country's rules

Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.

Open a free sample plan with these rules

Written by

Circuia team

Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.