Guide · Receptacle spacing · NEC
NEC receptacle spacing rules (210.52): the 6 ft / 12 ft rule, room by room
NEC 210.52(A) requires receptacles in living rooms, bedrooms and similar rooms so that no point along the floor line of a wall is more than 6 ft from one. Since each receptacle covers 6 ft on either side, that is the “6 ft / 12 ft rule”. This guide explains what counts as wall space, the rules for hallways, bathrooms, laundry, garages, outdoors and basements, and works through a 12 × 14 ft bedroom, for homeowners drawing plans for a permit and the electricians who review them.
Updated on Last checked NEC (NFPA 70) 2023
Key facts
- 016 ft rule (210.52(A)(1)): no point along a wall space more than 6 ft from a receptacle, so receptacles at most 12 ft apart and within 6 ft of each door.
- 02Wall space (210.52(A)(2)): any wall 2 ft wide or more, measured around corners and broken by doorways, fireplaces and fixed cabinets.
- 03Receptacles more than 5.5 ft above the floor, inside appliances or part of a luminaire do not count; floor receptacles count only within 18 in of the wall.
- 04Hallways 10 ft or longer need one receptacle; foyers over 60 ft² need one on each wall space of 3 ft or more.
- 05Bathroom: one within 3 ft of each basin; garage: one per vehicle bay; outdoors: front and back, no higher than 6 ft 6 in.
The 6 ft / 12 ft rule in habitable rooms (210.52(A)(1))
The rule applies to living rooms, family rooms, dining rooms, bedrooms, dens and similar habitable rooms, and to kitchen walls outside the countertop. It is written as a distance, not a count: walk along the floor line of every wall and check that you are never more than 6 ft (72 in, about 1.8 m) from a receptacle. The usual explanation is that a lamp or appliance with a 6 ft cord can then reach an outlet from anywhere along the wall without an extension cord.
Two consequences follow. The first receptacle after a door, a fireplace or the end of a wall space must be within 6 ft of it, and two receptacles on the same wall space can be at most 12 ft apart. You may of course install more; the code sets a minimum, and most people want more than the minimum near beds, desks and the TV wall.
What counts as wall space (210.52(A)(2))
A wall space is any wall at least 2 ft wide, unbroken along the floor line. It runs continuously around corners, so an L or U of walls is a single wall space. It is broken by doorways, by fireplaces and similar openings and by fixed cabinets that reach the floor. A 2 ft stretch of wall between two doors is its own wall space and needs a receptacle within reach; a section narrower than 2 ft can be ignored.
- Doorways, fireplaces and fixed cabinets break the wall space; the wall on each side is measured on its own.
- Fixed panels in exterior walls, such as fixed glass, are commonly counted as wall space, while sliding panels are treated like doors. Check the exact wording of 210.52(A)(2) in the edition your jurisdiction adopted, or ask your inspector.
| Receptacle | Counts? |
|---|---|
| Wall receptacle up to 5.5 ft above the floor | Yes |
| Receptacle more than 5.5 ft above the floor | No |
| Floor receptacle within 18 in of the wall | Yes |
| Floor receptacle farther than 18 in from the wall | No |
| Receptacle that is part of a luminaire or appliance, or inside a cabinet | No |
Worked example: a 12 × 14 ft bedroom
Take a 12 × 14 ft bedroom with a single 3 ft entry door and no closet in the room. The perimeter is 52 ft. The door breaks the wall line, so the room has one continuous wall space of 49 ft, starting at one side of the door, running around the three other walls and coming back to the other side.
- Each receptacle covers 6 ft on either side, so 12 ft of wall line.
- 4 receptacles cover 48 ft, one foot short of 49 ft.
- So the minimum is 5 receptacles: the first within 6 ft of the door jamb, then no more than 12 ft apart, the last within 6 ft of the other jamb.
- If the room also had a closet door, the wall line would split into two wall spaces, each with its own count, and the total could change.
| Step | Value |
|---|---|
| Perimeter | 52 ft |
| Minus the doorway | 49 ft of wall space |
| Coverage per receptacle | 12 ft (6 ft each side) |
| Minimum receptacles | 5 |
Hallways and foyers (210.52(H) and (I))
A hallway 10 ft long or more, measured along its centerline, needs at least one receptacle. A foyer that is not part of a hallway and has an area over 60 ft² needs a receptacle on each wall space 3 ft wide or more.
Bathrooms, laundry, garages, outdoors and basements
| Location | Minimum | Section |
|---|---|---|
| Bathroom | At least one within 3 ft of the outside edge of each basin, on a wall or partition next to it (or on the basin cabinet, no more than 12 in below its top); on a 20 A bathroom circuit | 210.52(D), 210.11(C)(3) |
| Laundry | At least one in each laundry area, on the 20 A laundry circuit; usually placed within 6 ft of the washer | 210.52(F), 210.11(C)(2) |
| Garage | At least one per vehicle bay, no higher than 5.5 ft above the floor, on a 20 A garage circuit | 210.52(G)(1), 210.11(C)(4) |
| Outdoors | At least one at the front and one at the back of a one- or two-family dwelling, readily accessible from grade and no higher than 6 ft 6 in; one on each balcony, deck or porch accessible from inside | 210.52(E) |
| Basement | At least one in each unfinished portion; finished, habitable parts follow the 6 ft rule | 210.52(G)(3) |
| HVAC equipment | A 125 V receptacle within 25 ft of the equipment, on the same level | 210.63 |
In bathrooms, check also how close a receptacle may be to a bathtub or shower: the NEC limits receptacles in the zone around the tub rim and shower threshold (406.9(C)). The exact wording depends on the edition, so confirm the distance with your inspector. All bathroom, garage, outdoor, laundry and unfinished-basement receptacles need GFCI protection (210.8(A)); outdoor receptacles in wet locations are weather-resistant with an in-use cover (406.9).
Kitchens follow a different rule
Along kitchen walls the 6 ft rule applies, but countertops have their own, tighter rule: no point along the wall line of a counter more than 24 in from a receptacle (210.52(C)(1)), on at least two 20 A small-appliance circuits. Islands and peninsulas changed in NEC 2023. See our kitchen countertop receptacle guide and the NEC 2023 overview for homes.
Residential electrical plan software that applies 210.52 for you
In a Circuia project set to the United States, Equip the rooms places receptacles by the 6 ft wall rule of 210.52, the 24 in countertop rule, one within 3 ft of each basin and one in hallways of 10 ft or more. You then move them where furniture allows. Auto-wire groups them into 15 A (14 AWG) and 20 A (12 AWG) circuits, with the kitchen countertop on two 20 A small-appliance circuits.
The NEC compliance check flags missing GFCI and AFCI protection (210.8, 210.12), receptacles that are not tamper-resistant and missing smoke alarms. The PDF prints on Letter paper in feet and inches, with a panel schedule that serves as the 408.4 circuit directory. Draw your plan to the NEC.
Common mistakes
- Counting receptacles per room instead of measuring every wall space.
- Forgetting the short wall between two doors when it is 2 ft or wider.
- Counting a receptacle above 5.5 ft, inside a cabinet or built into a light fixture.
- Skipping the hallway receptacle in a hallway of 10 ft or more.
- Putting the bathroom receptacle more than 3 ft from the basin, or on a 15 A general circuit.
Frequently asked questions
What is the 6 ft / 12 ft receptacle rule?
Does a door break the wall space?
How many receptacles does a 12 by 14 ft bedroom need?
Does a hallway need a receptacle?
How close to the sink must a bathroom receptacle be?
Design aid
Design the installation with this country's rules
Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.
Written by
Circuia team
Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.
Published · updated
Sources
Sources used for this page, official texts first:
Related pages
- GuideNEC 2023 for homes: the residential rules that matter (National Electrical Code)NEC 2023 for one- and two-family homes: required circuits, receptacle spacing, GFCI/AFCI, wire sizes, panel and permits. Plus a free NEC compliance check.
- GuideKitchen countertop receptacle requirements (NEC 2023): spacing, islands, circuits and GFCINEC 2023 kitchen rules: the 24 in countertop receptacle rule, islands and peninsulas, two 20 A small-appliance circuits, GFCI on every kitchen receptacle.