Code · United States

NEC 2023 for homes: the residential rules that matter (National Electrical Code)

The National Electrical Code (NEC, NFPA 70) is the model wiring code most US states and cities adopt for houses. The 2023 edition is the most widely adopted. For a home it decides which branch circuits you need (two 20 A small-appliance circuits, laundry, bathroom, garage), where receptacles go (the 6 ft wall rule, the 24 in countertop rule), which outlets need GFCI or AFCI protection, and what the inspector checks. This guide is written for homeowners drawing plans for a permit and for electricians who want a quick reference.

Updated on Last checked NEC (NFPA 70) 2023

Key facts

  • 01The NEC is a model code: it only applies once your state or city adopts it. 2023 is the most adopted edition; Massachusetts, Minnesota, Texas and Washington have moved to 2026; some places are still on 2020 or older.
  • 02Homes are fed 120/240 V split-phase, 60 Hz: 120 V circuits on one leg, 240 V loads (range, dryer, water heater, EV) on a two-pole breaker.
  • 03Required circuits (210.11(C)): at least 2 × 20 A small-appliance circuits for the kitchen and dining area, plus a 20 A laundry, a 20 A bathroom and a 20 A garage circuit.
  • 04Receptacles (210.52): no point along a wall more than 6 ft from a receptacle; no point along a countertop more than 24 in.
  • 05Since NEC 2023 all kitchen receptacles need GFCI protection (210.8(A)); AFCI covers 120 V 10/15/20 A circuits in bedrooms, living areas, kitchens, hallways and laundry (210.12(A)).
  • 06Copper wire vs breaker (240.4(D)): 14 AWG → 15 A, 12 AWG → 20 A, 10 AWG → 30 A.

NEC editions and state adoption: which code applies to your house?

NFPA publishes a new NEC every three years. The code has no force of law on its own: a state, county or city adopts an edition, often with local amendments, and its building or electrical department enforces it. That department is the AHJ, the authority having jurisdiction. The edition that applies to your project is usually the one in force on the date you apply for the permit (Massachusetts and Minnesota, for example, tie the 2026 edition to the permit application date).

NEC editions relevant to houses (status reported by public sources, October 2026)
EditionWhere (examples, verify per address)What it means for a house
NEC 2026Massachusetts, Minnesota, Texas (with a local exception on 210.8(F)), Washington (delayed effective date 31/12/2026); some citiesSmall changes for homes: load calculations move from Article 220 to Article 120, outdoor-outlet GFCI up to 60 A, no receptacle in the 24 in below an island countertop
NEC 2023The largest group of states (about 20 had completed adoption by October 2025 according to NFPA figures reported by EC&M, more since), e.g. California's 2025 code based on itThe reference of this guide: all kitchen receptacles GFCI, island receptacle optional with a provision for a future one, AFCI extended to 10 A circuits
NEC 2020A minority still updatingFirst edition requiring the outdoor emergency disconnect (230.85), whole-house surge protection (230.67) and the 20 A garage circuit
2017 or older / local onlyA few states, and states where only cities and counties adopt a codeAsk the permit office which edition and amendments apply
Adoption changes often and lists in trade press disagree. Never rely on a table like this one: ask your permit office.

Many states adopt the International Residential Code (IRC) for one- and two-family homes. Its electrical chapters (E3401–E4304 in the 2024 IRC) are derived from NEC 2023, so the receptacle rules in E3901 and the GFCI/AFCI rules in E3902 read almost the same. Some states delete those chapters and point straight to the NEC.

Split-phase 120/240 V service, grounding and service size

A US house receives 120/240 V single-phase, 3-wire, 60 Hz: two hot legs (L1 and L2) and a neutral. Each 120 V branch circuit uses one leg and the neutral on a single-pole breaker; 240 V loads use both legs on a two-pole, common-trip breaker (240.15(B)). Keeping the 120 V loads spread over both legs keeps the panel balanced. The neutral is bonded to ground only at the service disconnect (250.24(A)(5)); a subpanel keeps neutral and ground bars separate, fed by a 4-wire feeder.

  • Service size: at least 100 A for a one-family dwelling (230.79(C)); 200 A is the usual choice for new homes, larger services for all-electric homes. The size is justified by a load calculation (220.40 onward, or the optional method of 220.82; Article 120 in NEC 2026).
  • Emergency disconnect (230.85, NEC 2020 onward): one- and two-family dwellings need an outdoor, readily accessible disconnect marked “EMERGENCY DISCONNECT”.
  • Surge protection (230.67, NEC 2020 onward): a Type 1 or Type 2 SPD in or next to the service equipment, also when a service is replaced (2023).
  • Grounding electrode system (250.50–250.53): bond every electrode present, metal water pipe, concrete-encased electrode, ground rods of 8 ft; a single rod usually needs a second one at least 6 ft away.

Required branch circuits (210.11) and dedicated appliance circuits

Article 210 sets a short list of circuits every dwelling must have. Everything else, general lighting and the receptacles of bedrooms and living areas, is sized from the general lighting load of 3 VA per ft² of floor area (220.41), which gives the minimum number of 15 A or 20 A general-purpose circuits. The NEC sets no maximum number of receptacles per circuit in a dwelling; electricians commonly stop around 8 to 12, and some local amendments set limits, so check with your inspector.

Circuits a house needs, with the usual sizes
CircuitRuleSection
Small-appliance (kitchen, pantry, dining)At least 2 × 20 A, 12 AWG; countertop receptacles on at least two of them; no other outlets210.11(C)(1), 210.52(B)
LaundryAt least 1 × 20 A for the laundry receptacles only210.11(C)(2)
BathroomAt least 1 × 20 A for bathroom receptacles (or one 20 A circuit serving a single bathroom entirely)210.11(C)(3)
GarageAt least 1 × 20 A for the garage receptacles; may also serve readily accessible outdoor receptacles210.11(C)(4)
Range40 A / 8 AWG two-pole 240 V (or 50 A / 6 AWG for larger ranges), 4-wire220.55, 250.140
Clothes dryer30 A / 10 AWG two-pole, 4-wire220.54, 250.140
Water heater (4,500 W)Continuous load at 125 % → 30 A / 10 AWG two-pole422.13
EV charger (32 A EVSE)Individual circuit, breaker at least 125 % of the charger rating → 40 A / 8 AWG625.40, 625.41
Dishwasher / disposal15 or 20 A, shared or separate per the manufacturer's instructions422.16(B)
HVAC equipmentWire to the nameplate MCA, breaker no larger than the MOCP440.4(B), 440.22
Range and appliance sizes depend on the nameplate. Values marked as usual practice are common choices, not code minimums.

Where receptacles go: the 6 ft wall rule and the 24 in countertop rule (210.52)

In living rooms, bedrooms, dining rooms, dens and similar rooms, receptacles are placed so that no point along the floor line of a wall space is more than 6 ft from one (210.52(A)(1)). In practice that means a receptacle every 12 ft at most. A wall space is any wall at least 2 ft wide, measured continuously around corners and broken by doorways, fireplaces and fixed cabinets. Our receptacle spacing guide works through a full bedroom.

Receptacle outlets required in a dwelling (NEC 2023, IRC E3901)
LocationRequirementSection
Habitable roomsNo point of a wall space more than 6 ft from a receptacle210.52(A)
Kitchen countertopsEvery counter space 12 in or wider; no point more than 24 in from a receptacle; no higher than 20 in above the counter210.52(C)
Islands and peninsulasReceptacle optional since 2023, but a provision for a future one is required210.52(C)(2)
BathroomsAt least one within 3 ft of the outside edge of each basin210.52(D)
OutdoorsAt least one at the front and one at the back, no higher than 6 ft 6 in above grade; one on each balcony, deck or porch reachable from inside210.52(E)
LaundryAt least one in each laundry area210.52(F)
Garage, basementOne per vehicle bay; one in each unfinished part of a basement210.52(G)
Hallways, foyersHallways 10 ft or longer get one; foyers over 60 ft² get one on each wall space of 3 ft or more210.52(H), (I)

The kitchen has its own rules, covered in detail in our kitchen countertop receptacle guide. Every habitable room, kitchen, bathroom, hallway, stairway, attached garage and outdoor entrance also needs at least one wall-switch-controlled lighting outlet (210.70); in rooms other than kitchens and bathrooms a switched receptacle may stand in for it.

GFCI and AFCI protection by room (210.8 and 210.12)

US homes do not have a whole-house residual current device. Shock protection comes from GFCI devices (about 5 mA, per circuit at the breaker or per receptacle), and fire protection from AFCI breakers. A dual-function breaker provides both, which is the usual answer for kitchen and laundry circuits. GFCI devices must be readily accessible.

GFCI and AFCI requirements by room in NEC 2023
RoomGFCI (210.8(A))AFCI (210.12(A))
KitchenAll 125–250 V receptacles (new in 2023), plus the dishwasherYes
BathroomAll receptaclesNot listed in 210.12(A); some jurisdictions add it, check locally
Bedrooms, living, dining, family rooms, closets, hallwaysOnly receptacles within 6 ft of a sinkYes
Laundry areaYesYes
Garage, outdoors, unfinished basement, crawl spaceYesNot required for garages and outdoors
Any receptacle within 6 ft of a sink, bathtub or showerYesDepends on the room
NEC 2023 also lists ranges, wall ovens, cooktops, dryers and microwave ovens for GFCI protection (422.5(A)); many AHJs have amended some of these out. Check with your inspector.

Tamper-resistant (TR) receptacles are required for 15 A and 20 A, 125 V and 250 V non-locking receptacles throughout a dwelling (406.12), with narrow exceptions such as receptacles more than 5.5 ft above the floor. Outdoors, receptacles in wet locations are weather-resistant with an in-use (bubble) cover (406.9).

Conductor size vs breaker: the AWG table

Most house wiring is copper NM-B cable (“Romex”), used at its 60 °C ampacity (334.80). For the small sizes, 240.4(D) caps the breaker regardless of the ampacity table. The table below is what Circuia's auto-wire applies.

Copper NM-B: largest breaker per wire size (240.4(D), 310.16 at 60 °C)
Wire sizeLargest breakerTypical use
14 AWG15 ALighting and general-purpose 15 A circuits (14/2)
12 AWG20 AReceptacles, small-appliance, bathroom, laundry, garage (12/2)
10 AWG30 AWater heater (10/2), dryer (10/3)
8 AWG40 ARange or 40 A EV circuit (8/3)
6 AWG50 ALarger range; capped at 50 A in NM-B (55 A ampacity)
Voltage drop of 3 % on a branch circuit and 5 % overall appears only as an informational note in the NEC: good practice, not an enforceable rule.

The panel: breakers, working space and circuit directory

  • Working space in front of the panel (110.26(A)): 30 in wide (or the width of the equipment), 36 in deep and 6.5 ft high, kept clear.
  • Location: not in a clothes closet, not in a bathroom and not over the steps of a stairway (240.24(D), (E), (F)); readily accessible.
  • Circuit directory (408.4(A)): every circuit legibly identified by its purpose and location, spares included. Inspectors check it at the final.
  • Multiwire branch circuits (12/3 cable): the two hots on opposite legs with a two-pole breaker or listed handle tie, so they disconnect together (210.4).
  • Tandem breakers only where the panel is listed for them (408.54).

Smoke and carbon monoxide alarms (IRC R314 / R315)

Alarms come from the residential building code rather than the NEC. Smoke alarms go in each sleeping room, outside each sleeping area near the bedrooms and on every story, including basements. They are powered from the building wiring with battery backup and interconnected, so one alarm sounds them all. Homes with a fuel-burning appliance or an attached garage also need carbon monoxide alarms outside each sleeping area; combination smoke/CO alarms are allowed. Exact placement details vary with the edition your state adopted.

Permits and inspections: what to expect

  1. Permit from the city or county before work starts. Most jurisdictions require a licensed electrical contractor; many let owners pull a homeowner permit for their own owner-occupied single-family home, but the rules vary from state to state.
  2. Rough-in inspection, before insulation and drywall: box locations, cable stapling, nail plates, grounding and bonding, conductor sizes vs breakers.
  3. Final inspection: devices installed (TR, WR, GFCI, AFCI tested), panel directory complete, working space clear, smoke and CO alarms working.
  4. The utility then sets the meter or releases the service.

A clear floor plan with receptacle locations, a circuit list and a panel schedule makes both the permit review and the inspection faster. That is the drawing set Circuia produces.

Residential electrical plan software with an NEC compliance check

Choose United States when you create a project in Circuia. Equip the rooms places receptacles following the 6 ft wall rule of 210.52, the 24 in countertop rule, one within 3 ft of each basin and one in hallways of 10 ft or more. Auto-wire puts the kitchen countertop receptacles on two 20 A small-appliance circuits, sizes 14 AWG on 15 A and 12 AWG on 20 A, and gives the range, water heater and EV charger a 240 V two-pole breaker.

The compliance check then flags missing GFCI and AFCI protection under 210.8 and 210.12, non-tamper-resistant receptacles and missing smoke alarms. The PDF export is on Letter paper with imperial units and includes a panel schedule that doubles as the circuit directory of 408.4.

Common mistakes

  • Assuming the latest NEC applies: the edition is the one your state or city adopted, with its amendments.
  • Putting the refrigerator, dishwasher or lighting on a small-appliance circuit (only kitchen, pantry and dining receptacles belong there, with a few exceptions).
  • Forgetting GFCI on kitchen receptacles that do not serve the countertop (required since NEC 2023).
  • Using 14 AWG wire on a 20 A breaker.
  • Counting a receptacle behind a fixed cabinet or more than 5.5 ft above the floor toward the 6 ft rule.
  • Leaving the panel directory blank or vague (“kitchen”, “misc.”).

Frequently asked questions

Which edition of the NEC applies to my house?

The edition your state, county or city adopted, usually the one in force on the date you apply for the permit. NEC 2023 is the most adopted; Massachusetts, Minnesota, Texas and Washington use NEC 2026; some places are still on 2020 or older, and local amendments are common. Ask your permit office, which represents the authority having jurisdiction (AHJ).

Can a homeowner do their own electrical work in the US?

Many jurisdictions issue a homeowner permit for work on your own owner-occupied single-family home, but the rules vary by state and city, and some require a licensed electrician for all work. Either way you need a permit and inspections. Check with your local building or electrical department before starting, and never work on live circuits.

How many circuits does a kitchen need under the NEC?

At least 2 small-appliance branch circuits of 20 A serving the kitchen, pantry and dining receptacles, with the countertop receptacles on at least two of them (210.11(C)(1), 210.52(B)). The range, dishwasher, disposal, microwave and refrigerator usually get circuits of their own, sized to the manufacturer's instructions.

Where is GFCI protection required in a house?

Under NEC 2023 (210.8(A)): bathrooms, kitchens (all receptacles), garages, outdoors, crawl spaces, unfinished basements, laundry areas and any receptacle within 6 ft of a sink, bathtub or shower, plus the dishwasher. NEC 2023 also lists ranges, ovens, cooktops, dryers and microwaves, which some jurisdictions have amended out. Check the local amendments.

What size wire for a 20 amp circuit?

12 AWG copper. The small-conductor rule of 240.4(D) limits 14 AWG copper to a 15 A breaker, 12 AWG to 20 A and 10 AWG to 30 A, whatever the ampacity table says. Kitchen small-appliance, bathroom, laundry and garage circuits are 20 A, so they are wired in 12 AWG.

Does Circuia replace an electrician or the inspection?

No. Circuia's US rules are built from public sources and not reviewed by a US master electrician. It helps you draw a residential electrical plan, check it against NEC 2023 rules and export a permit-ready drawing with a panel schedule. A licensed electrician and the local inspector remain responsible for the installation.

Design aid

Design the installation with this country's rules

Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.

Open a free sample plan with these rules

Written by

Circuia team

Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.