Code · United States
NEC 2023 for homes: the residential rules that matter (National Electrical Code)
The National Electrical Code (NEC, NFPA 70) is the model wiring code most US states and cities adopt for houses. The 2023 edition is the most widely adopted. For a home it decides which branch circuits you need (two 20 A small-appliance circuits, laundry, bathroom, garage), where receptacles go (the 6 ft wall rule, the 24 in countertop rule), which outlets need GFCI or AFCI protection, and what the inspector checks. This guide is written for homeowners drawing plans for a permit and for electricians who want a quick reference.
Updated on Last checked NEC (NFPA 70) 2023
Key facts
- 01The NEC is a model code: it only applies once your state or city adopts it. 2023 is the most adopted edition; Massachusetts, Minnesota, Texas and Washington have moved to 2026; some places are still on 2020 or older.
- 02Homes are fed 120/240 V split-phase, 60 Hz: 120 V circuits on one leg, 240 V loads (range, dryer, water heater, EV) on a two-pole breaker.
- 03Required circuits (210.11(C)): at least 2 × 20 A small-appliance circuits for the kitchen and dining area, plus a 20 A laundry, a 20 A bathroom and a 20 A garage circuit.
- 04Receptacles (210.52): no point along a wall more than 6 ft from a receptacle; no point along a countertop more than 24 in.
- 05Since NEC 2023 all kitchen receptacles need GFCI protection (210.8(A)); AFCI covers 120 V 10/15/20 A circuits in bedrooms, living areas, kitchens, hallways and laundry (210.12(A)).
- 06Copper wire vs breaker (240.4(D)): 14 AWG → 15 A, 12 AWG → 20 A, 10 AWG → 30 A.
NEC editions and state adoption: which code applies to your house?
NFPA publishes a new NEC every three years. The code has no force of law on its own: a state, county or city adopts an edition, often with local amendments, and its building or electrical department enforces it. That department is the AHJ, the authority having jurisdiction. The edition that applies to your project is usually the one in force on the date you apply for the permit (Massachusetts and Minnesota, for example, tie the 2026 edition to the permit application date).
| Edition | Where (examples, verify per address) | What it means for a house |
|---|---|---|
| NEC 2026 | Massachusetts, Minnesota, Texas (with a local exception on 210.8(F)), Washington (delayed effective date 31/12/2026); some cities | Small changes for homes: load calculations move from Article 220 to Article 120, outdoor-outlet GFCI up to 60 A, no receptacle in the 24 in below an island countertop |
| NEC 2023 | The largest group of states (about 20 had completed adoption by October 2025 according to NFPA figures reported by EC&M, more since), e.g. California's 2025 code based on it | The reference of this guide: all kitchen receptacles GFCI, island receptacle optional with a provision for a future one, AFCI extended to 10 A circuits |
| NEC 2020 | A minority still updating | First edition requiring the outdoor emergency disconnect (230.85), whole-house surge protection (230.67) and the 20 A garage circuit |
| 2017 or older / local only | A few states, and states where only cities and counties adopt a code | Ask the permit office which edition and amendments apply |
Many states adopt the International Residential Code (IRC) for one- and two-family homes. Its electrical chapters (E3401–E4304 in the 2024 IRC) are derived from NEC 2023, so the receptacle rules in E3901 and the GFCI/AFCI rules in E3902 read almost the same. Some states delete those chapters and point straight to the NEC.
Split-phase 120/240 V service, grounding and service size
A US house receives 120/240 V single-phase, 3-wire, 60 Hz: two hot legs (L1 and L2) and a neutral. Each 120 V branch circuit uses one leg and the neutral on a single-pole breaker; 240 V loads use both legs on a two-pole, common-trip breaker (240.15(B)). Keeping the 120 V loads spread over both legs keeps the panel balanced. The neutral is bonded to ground only at the service disconnect (250.24(A)(5)); a subpanel keeps neutral and ground bars separate, fed by a 4-wire feeder.
- Service size: at least 100 A for a one-family dwelling (230.79(C)); 200 A is the usual choice for new homes, larger services for all-electric homes. The size is justified by a load calculation (220.40 onward, or the optional method of 220.82; Article 120 in NEC 2026).
- Emergency disconnect (230.85, NEC 2020 onward): one- and two-family dwellings need an outdoor, readily accessible disconnect marked “EMERGENCY DISCONNECT”.
- Surge protection (230.67, NEC 2020 onward): a Type 1 or Type 2 SPD in or next to the service equipment, also when a service is replaced (2023).
- Grounding electrode system (250.50–250.53): bond every electrode present, metal water pipe, concrete-encased electrode, ground rods of 8 ft; a single rod usually needs a second one at least 6 ft away.
Required branch circuits (210.11) and dedicated appliance circuits
Article 210 sets a short list of circuits every dwelling must have. Everything else, general lighting and the receptacles of bedrooms and living areas, is sized from the general lighting load of 3 VA per ft² of floor area (220.41), which gives the minimum number of 15 A or 20 A general-purpose circuits. The NEC sets no maximum number of receptacles per circuit in a dwelling; electricians commonly stop around 8 to 12, and some local amendments set limits, so check with your inspector.
| Circuit | Rule | Section |
|---|---|---|
| Small-appliance (kitchen, pantry, dining) | At least 2 × 20 A, 12 AWG; countertop receptacles on at least two of them; no other outlets | 210.11(C)(1), 210.52(B) |
| Laundry | At least 1 × 20 A for the laundry receptacles only | 210.11(C)(2) |
| Bathroom | At least 1 × 20 A for bathroom receptacles (or one 20 A circuit serving a single bathroom entirely) | 210.11(C)(3) |
| Garage | At least 1 × 20 A for the garage receptacles; may also serve readily accessible outdoor receptacles | 210.11(C)(4) |
| Range | 40 A / 8 AWG two-pole 240 V (or 50 A / 6 AWG for larger ranges), 4-wire | 220.55, 250.140 |
| Clothes dryer | 30 A / 10 AWG two-pole, 4-wire | 220.54, 250.140 |
| Water heater (4,500 W) | Continuous load at 125 % → 30 A / 10 AWG two-pole | 422.13 |
| EV charger (32 A EVSE) | Individual circuit, breaker at least 125 % of the charger rating → 40 A / 8 AWG | 625.40, 625.41 |
| Dishwasher / disposal | 15 or 20 A, shared or separate per the manufacturer's instructions | 422.16(B) |
| HVAC equipment | Wire to the nameplate MCA, breaker no larger than the MOCP | 440.4(B), 440.22 |
Where receptacles go: the 6 ft wall rule and the 24 in countertop rule (210.52)
In living rooms, bedrooms, dining rooms, dens and similar rooms, receptacles are placed so that no point along the floor line of a wall space is more than 6 ft from one (210.52(A)(1)). In practice that means a receptacle every 12 ft at most. A wall space is any wall at least 2 ft wide, measured continuously around corners and broken by doorways, fireplaces and fixed cabinets. Our receptacle spacing guide works through a full bedroom.
| Location | Requirement | Section |
|---|---|---|
| Habitable rooms | No point of a wall space more than 6 ft from a receptacle | 210.52(A) |
| Kitchen countertops | Every counter space 12 in or wider; no point more than 24 in from a receptacle; no higher than 20 in above the counter | 210.52(C) |
| Islands and peninsulas | Receptacle optional since 2023, but a provision for a future one is required | 210.52(C)(2) |
| Bathrooms | At least one within 3 ft of the outside edge of each basin | 210.52(D) |
| Outdoors | At least one at the front and one at the back, no higher than 6 ft 6 in above grade; one on each balcony, deck or porch reachable from inside | 210.52(E) |
| Laundry | At least one in each laundry area | 210.52(F) |
| Garage, basement | One per vehicle bay; one in each unfinished part of a basement | 210.52(G) |
| Hallways, foyers | Hallways 10 ft or longer get one; foyers over 60 ft² get one on each wall space of 3 ft or more | 210.52(H), (I) |
The kitchen has its own rules, covered in detail in our kitchen countertop receptacle guide. Every habitable room, kitchen, bathroom, hallway, stairway, attached garage and outdoor entrance also needs at least one wall-switch-controlled lighting outlet (210.70); in rooms other than kitchens and bathrooms a switched receptacle may stand in for it.
GFCI and AFCI protection by room (210.8 and 210.12)
US homes do not have a whole-house residual current device. Shock protection comes from GFCI devices (about 5 mA, per circuit at the breaker or per receptacle), and fire protection from AFCI breakers. A dual-function breaker provides both, which is the usual answer for kitchen and laundry circuits. GFCI devices must be readily accessible.
| Room | GFCI (210.8(A)) | AFCI (210.12(A)) |
|---|---|---|
| Kitchen | All 125–250 V receptacles (new in 2023), plus the dishwasher | Yes |
| Bathroom | All receptacles | Not listed in 210.12(A); some jurisdictions add it, check locally |
| Bedrooms, living, dining, family rooms, closets, hallways | Only receptacles within 6 ft of a sink | Yes |
| Laundry area | Yes | Yes |
| Garage, outdoors, unfinished basement, crawl space | Yes | Not required for garages and outdoors |
| Any receptacle within 6 ft of a sink, bathtub or shower | Yes | Depends on the room |
Tamper-resistant (TR) receptacles are required for 15 A and 20 A, 125 V and 250 V non-locking receptacles throughout a dwelling (406.12), with narrow exceptions such as receptacles more than 5.5 ft above the floor. Outdoors, receptacles in wet locations are weather-resistant with an in-use (bubble) cover (406.9).
Conductor size vs breaker: the AWG table
Most house wiring is copper NM-B cable (“Romex”), used at its 60 °C ampacity (334.80). For the small sizes, 240.4(D) caps the breaker regardless of the ampacity table. The table below is what Circuia's auto-wire applies.
| Wire size | Largest breaker | Typical use |
|---|---|---|
| 14 AWG | 15 A | Lighting and general-purpose 15 A circuits (14/2) |
| 12 AWG | 20 A | Receptacles, small-appliance, bathroom, laundry, garage (12/2) |
| 10 AWG | 30 A | Water heater (10/2), dryer (10/3) |
| 8 AWG | 40 A | Range or 40 A EV circuit (8/3) |
| 6 AWG | 50 A | Larger range; capped at 50 A in NM-B (55 A ampacity) |
The panel: breakers, working space and circuit directory
- Working space in front of the panel (110.26(A)): 30 in wide (or the width of the equipment), 36 in deep and 6.5 ft high, kept clear.
- Location: not in a clothes closet, not in a bathroom and not over the steps of a stairway (240.24(D), (E), (F)); readily accessible.
- Circuit directory (408.4(A)): every circuit legibly identified by its purpose and location, spares included. Inspectors check it at the final.
- Multiwire branch circuits (12/3 cable): the two hots on opposite legs with a two-pole breaker or listed handle tie, so they disconnect together (210.4).
- Tandem breakers only where the panel is listed for them (408.54).
Smoke and carbon monoxide alarms (IRC R314 / R315)
Alarms come from the residential building code rather than the NEC. Smoke alarms go in each sleeping room, outside each sleeping area near the bedrooms and on every story, including basements. They are powered from the building wiring with battery backup and interconnected, so one alarm sounds them all. Homes with a fuel-burning appliance or an attached garage also need carbon monoxide alarms outside each sleeping area; combination smoke/CO alarms are allowed. Exact placement details vary with the edition your state adopted.
Permits and inspections: what to expect
- Permit from the city or county before work starts. Most jurisdictions require a licensed electrical contractor; many let owners pull a homeowner permit for their own owner-occupied single-family home, but the rules vary from state to state.
- Rough-in inspection, before insulation and drywall: box locations, cable stapling, nail plates, grounding and bonding, conductor sizes vs breakers.
- Final inspection: devices installed (TR, WR, GFCI, AFCI tested), panel directory complete, working space clear, smoke and CO alarms working.
- The utility then sets the meter or releases the service.
A clear floor plan with receptacle locations, a circuit list and a panel schedule makes both the permit review and the inspection faster. That is the drawing set Circuia produces.
Residential electrical plan software with an NEC compliance check
Choose United States when you create a project in Circuia. Equip the rooms places receptacles following the 6 ft wall rule of 210.52, the 24 in countertop rule, one within 3 ft of each basin and one in hallways of 10 ft or more. Auto-wire puts the kitchen countertop receptacles on two 20 A small-appliance circuits, sizes 14 AWG on 15 A and 12 AWG on 20 A, and gives the range, water heater and EV charger a 240 V two-pole breaker.
The compliance check then flags missing GFCI and AFCI protection under 210.8 and 210.12, non-tamper-resistant receptacles and missing smoke alarms. The PDF export is on Letter paper with imperial units and includes a panel schedule that doubles as the circuit directory of 408.4.
Common mistakes
- Assuming the latest NEC applies: the edition is the one your state or city adopted, with its amendments.
- Putting the refrigerator, dishwasher or lighting on a small-appliance circuit (only kitchen, pantry and dining receptacles belong there, with a few exceptions).
- Forgetting GFCI on kitchen receptacles that do not serve the countertop (required since NEC 2023).
- Using 14 AWG wire on a 20 A breaker.
- Counting a receptacle behind a fixed cabinet or more than 5.5 ft above the floor toward the 6 ft rule.
- Leaving the panel directory blank or vague (“kitchen”, “misc.”).
Frequently asked questions
Which edition of the NEC applies to my house?
Can a homeowner do their own electrical work in the US?
How many circuits does a kitchen need under the NEC?
Where is GFCI protection required in a house?
What size wire for a 20 amp circuit?
Does Circuia replace an electrician or the inspection?
Design aid
Design the installation with this country's rules
Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.
Written by
Circuia team
Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.
Published · updated
Sources
Sources used for this page, official texts first:
- NFPA 70, National Electrical Code 2023 — free read-only access
- NFPA 70, National Electrical Code 2026 — free read-only access
- ICC — IRC Section R314, smoke alarms (PDF)
- UL Code Authority — 2026 NEC dates and 210.8(F)
- Mass.gov — 527 CMR 12.00, Massachusetts Electrical Code amendments
- Minnesota DLI — 2026 NEC adoption
- TDLR — Texas adoption of the 2026 NEC
- EC&M — Unpacking key revisions to the 2026 NEC (adoption status)
- IAEI Magazine — Major changes in the 2023 NEC
- Mike Holt — Article 625, EV power transfer (PDF)
- Leviton Captain Code — NEC 2023, 220.53 / 220.57
Related pages
- GuideNEC receptacle spacing rules (210.52): the 6 ft / 12 ft rule, room by roomHow NEC 210.52 spaces receptacles in a house: the 6 ft / 12 ft rule, what counts as wall space, hallways, bathrooms, garages and a worked bedroom example.