Voltage drop calculator (mm² and AWG)

Choose the conductor size, the length and the current: the calculator gives the voltage drop in volts and percent and compares it with the limits of your country (3 % lighting / 5 % other in the UK, 3 % per branch circuit in the US).

Updated on BS 7671 · NEC

Inputs

Rules applied: BS 7671:2018+A4:2026 — United Kingdom (beta, IET Wiring Regulations 18th Edition) · beta rules, to be checked locally

m

One way.

A
Supply

Result

Voltage drop

3.2%

That is

7.4V

Lighting (≤ 3 %)Too high
Other uses (≤ 5 %)Within limit
Voltage at the end of the line≈ 223 V

Indicative calculation (copper, service resistivity). Limits for installations supplied from the public low-voltage network.

References

  • § BS 7671 Appendix 4, 6.4

Estimate for planning only. Switch off before any work and have it checked by a qualified electrician.

Next step · free

Turn this result into a real plan

Draw your rooms, place sockets and lights: Circuia checks every rule as you go and builds the board schedule.

Open the free editor →Free · no sign-up to start
</> Embed this tool on your website

Free, no sign-up. Paste this code into your page (blog, contractor site, forum): the tool shows up and stays up to date.

How it works

  • ΔU = b × (ρ × L / S × cos φ + λ × L × sin φ) × I with ρ = 0.023 Ω·mm²/m (copper in service) and λ = 0.08 mΩ/m.
  • b = 2 for single-phase and 120/240 V two-wire circuits, 1 for balanced three-phase (drop per phase).
  • Limits: BS 7671 Appendix 4 §6.4; NEC 210.19(A) Informational Note 4; HD 60364-5-52 Annex G elsewhere.

Frequently asked questions

What is the maximum voltage drop allowed?

UK: 3 % for lighting and 5 % for other uses from the origin of a public supply (BS 7671 Appendix 4). US: 3 % on a branch circuit and 5 % feeder + branch are recommendations of the NEC informational notes.

How do I reduce voltage drop?

Use a larger conductor, shorten the run, or split the load. Doubling the size roughly halves the drop.

Why is my result different from an online table?

Tables assume a temperature, a power factor and sometimes a different resistivity. This calculator uses copper in service conditions and lets you set cos φ.