What breaker and cable for my appliance?

Pick the appliance and its power: the calculator sizes its dedicated circuit for your country — breaker, cable (mm² or AWG), RCD type or GFCI — starting from the ratings the Circuia editor uses and upsizing for long runs and continuous loads.

Updated on BS 7671 · NEC

Inputs

Rules applied: BS 7671:2018+A4:2026 — United Kingdom (beta, IET Wiring Regulations 18th Edition) · beta rules, to be checked locally

W

Nameplate power (typical: 7,200 W).

m

One way.

Result

Breaker

32A

Cable

6mm²

Circuit voltage230 V
Calculated current31.3 A
Voltage drop1.57 % (≤ 5 %)
RCD30 mA type A

Estimate for a copper dedicated circuit. The appliance's installation manual and nameplate (MCA / MOCP) win.

References

  • § BS 7671 Reg. 433.1.1 + IET On-Site Guide Appendix A (cooker diversity)
  • § BS 7671 Reg. 433.1.1
  • § BS 7671 Appendix 4 (Table 4D5)

Estimate for planning only. Switch off before any work and have it checked by a qualified electrician.

Next step · free

Turn this result into a real plan

Open the editor with the Hob / cooktop / range placed on its dedicated circuit, then draw the rest of the home.

Open the editor with this result →Free · no sign-up to start
</> Embed this tool on your website

Free, no sign-up. Paste this code into your page (blog, contractor site, forum): the tool shows up and stays up to date.

How it works

  • The country's usual rating for the appliance is the starting point (e.g. cooker 32 A / 6 mm² in the UK, range 40 A / 8 AWG in the US).
  • Continuous loads (EV, US water heaters) are sized at 125 % (NEC 210.19 / 422.13 / 625.41) or above the charging current.
  • US ranges use the demand load of NEC Table 220.55; loads above 1,800 W go 240 V.
  • The voltage drop over the length can only make the cable bigger.

Frequently asked questions

What size cable for an electric cooker in the UK?

Usually 6 mm² on a 32 A breaker thanks to cooker diversity; large range cookers or long runs may need 10 mm² / 40–45 A.

What breaker for a 4,500 W water heater in the US?

4,500 W at 240 V is 18.75 A; at 125 % (NEC 422.13) that is 23.4 A, and Circuia uses the usual 30 A / 10 AWG circuit.

Which RCD type for a heat pump?

Single-phase inverter heat pumps usually need type F (or A as a minimum), three-phase inverters type B unless the manual says otherwise.

Design aid

For your actual home, move to the editor

Draw your home or describe it to the AI: Circuia places the points, checks the rules in real time and generates the consumer unit, single-line diagram and bill of materials.

Open the free editor