Cable size calculator (BS 7671 & NEC, mm² and AWG)

Enter the power (or current), the circuit length and its use: the calculator keeps the larger of two sizes — the one the breaker needs and the one that keeps the voltage drop within the limit of your country (3 % lighting / 5 % other in the UK, 3 % per branch circuit in the US).

Updated on BS 7671 · NEC

Inputs

Rules applied: BS 7671:2018+A4:2026 — United Kingdom (beta, IET Wiring Regulations 18th Edition) · beta rules, to be checked locally

I know
W
m

One way.

Use
Supply

Result

Recommended size

1.5mm²

Breaker

16A

Calculated current15.2 A · 230 V
Size imposed by the breaker1 mm²
Size to stay under 5 %1.5 mm²
Voltage drop4.06 % (9.3 V)
Voltage drop by size
SizeMax breakerΔU
1 mm²16 A6.09 %
1.5 mm²20 A4.06 %
2.5 mm²25 A2.43 %
4 mm²32 A1.52 %
6 mm²45 A1.01 %
10 mm²63 A0.61 %
16 mm²80 A0.38 %
25 mm²—0.24 %
35 mm²—0.17 %
50 mm²—0.12 %

Indicative estimate (copper, single circuit, no derating for installation method, temperature or grouping). Have it checked by an electrician.

References

  • § BS 7671 Appendix 4, 6.4
  • § BS 7671 — conductor / breaker table

Estimate for planning only. Switch off before any work and have it checked by a qualified electrician.

Next step · free

Turn this result into a real plan

Draw your rooms, place sockets and lights: Circuia checks every rule as you go and builds the board schedule.

Open the free editor →Free · no sign-up to start
</> Embed this tool on your website

Free, no sign-up. Paste this code into your page (blog, contractor site, forum): the tool shows up and stays up to date.

How it works

  • The current gives the breaker: the next standard rating above it (IEC 60898 or NEC 240.6(A)).
  • The breaker imposes a minimum conductor from the country's table (BS 7671 Appendix 4; NEC 310.16 60 °C column for NM-B).
  • The length can then require a bigger size to keep the voltage drop within the limit (BS 7671 Appendix 4 §6.4; NEC 210.19(A) Informational Note 4).
  • Voltage drop ΔU = b × (ρ × L / S × cos φ + λ × L × sin φ) × I, copper, b = 2 single-phase.

Frequently asked questions

What size cable for a 32 A breaker in the UK?

With twin-and-earth clipped direct, 32 A usually needs 4 mm² on a radial, or 6 mm² for a cooker circuit or long runs. The installation method, insulation and grouping can push it higher: check BS 7671 Appendix 4 with your electrician.

What gauge wire for a 20 amp circuit?

12 AWG copper (NEC 240.4(D)). For long runs the voltage drop may call for 10 AWG — the calculator checks it against the 3 % branch-circuit recommendation.

Does the calculator replace an electrician?

No. It ignores installation method, ambient temperature, grouping and aluminium conductors, which can all require larger sizes. A qualified electrician must validate the final choice.

Design aid

For your actual home, move to the editor

Draw your home or describe it to the AI: Circuia places the points, checks the rules in real time and generates the consumer unit, single-line diagram and bill of materials.

Open the free editor