EV charger sizing: breaker, cable, RCD and supply check

Choose the charger power and your supply: the calculator sizes the dedicated circuit (breaker, cable, RCD type) and checks that your main fuse, subscription or service can take it next to the rest of the house — or that you need load management.

Updated on BS 7671 · NEC

Inputs

Rules applied: BS 7671:2018+A4:2026 — United Kingdom (beta, IET Wiring Regulations 18th Edition) · beta rules, to be checked locally

W

Cooking, heating, water heater at the same time (W).

m

One way.

Result

Breaker

32A

Cable

6mm²

Your 100 A supply can take it (19 kW available).

Charging current32.2 A · 230 V
Design current (continuous load)32 A
RCD30 mA type A + 6 mA DC detection (RDC-DD), often built into the charger
Voltage drop1.6 % (≤ 5 %)
  • PME supply: open-PEN fault protection or an earth electrode (BS 7671 722.411.4.1).
  • New home chargers must be smart (Electric Vehicles (Smart Charge Points) Regulations 2021); notify the DNO.

Charging cost and payback of this charger

Estimate for a copper circuit. The charger's manual and the network operator's rules win; installation by a qualified installer.

References

  • § BS 7671 Section 722 (722.311, 722.531.3.101)
  • § BS 7671 722.411.4.1 (PEN fault / O-PEN)
  • § Electric Vehicles (Smart Charge Points) Regulations 2021

Estimate for planning only. Switch off before any work and have it checked by a qualified electrician.

Next step · free

Turn this result into a real plan

Open the editor with the EV charger placed on its own circuit and RCD, then add the rest of the home.

Open the editor with this result →Free · no sign-up to start
</> Embed this tool on your website

Free, no sign-up. Paste this code into your page (blog, contractor site, forum): the tool shows up and stays up to date.

How it works

  • Dedicated circuit for the charging point (BS 7671 722.311; NEC 625.40).
  • US: breaker and conductors at 125 % of the EVSE current (625.41) — 40 A charging needs a 50 A circuit.
  • RCD: type B, or type A + 6 mA DC detection (IEC 62955) — often built into the charger.
  • Supply check: supply capacity − house peak load ≥ charger power, else load management or an upgrade.

Frequently asked questions

What size breaker for a 7 kW charger?

7.4 kW is 32 A single-phase. In the UK it usually goes on a 32 A (or 40 A) breaker with 6 mm² or larger cable depending on length; in France 40 A / 10 mm².

What breaker for a 48 A EV charger in the US?

60 A: the circuit is sized at 125 % of the continuous load (NEC 625.41), with 6 AWG copper THHN in conduit or larger.

Do I need to upgrade my main fuse?

Not always: a charger with dynamic load management slows down when the house draws more, which avoids most upgrades.