Free tool · No sign-up
Conduit fill calculator (EMT, PVC, corrugated)
List the conductors: the calculator gives the smallest conduit that holds them — NEC Chapter 9 Table 1 fill with THHN areas for EMT and PVC in the US, and the usual one-third rule for metric corrugated conduits in Europe.
Updated on BS 7671 · NEC
Result
Minimum conduit
Ø 20mm
Allowed fill
33%
| Conduit | Fill | |
|---|---|---|
| Ø 16 mm | 58 % | ✕ |
| Ø 20 mm | 33 % | ✓ |
| Ø 25 mm | 20 % | ✓ |
| Ø 32 mm | 11 % | ✓ |
| Ø 40 mm | 7 % | ✓ |
| Ø 50 mm | 4 % | ✓ |
| Ø 63 mm | 3 % | ✓ |
Total conductor area ≤ 1/3 of the conduit's inner area, to pull the wires without damage and leave room to replace them.
Typical catalogue diameters: the manufacturer's figures win.
References
- § HD 60364-5-52 (522.8)
- § EN 61386
Estimate for planning only. Switch off before any work and have it checked by a qualified electrician.
Next step · free
Turn this result into a real plan
Draw your rooms, place sockets and lights: Circuia checks every rule as you go and builds the board schedule.
</> Embed this tool on your website
Free, no sign-up. Paste this code into your page (blog, contractor site, forum): the tool shows up and stays up to date.
How it works
- US: 53 % fill for 1 conductor, 31 % for 2, 40 % for 3 or more (NEC Chapter 9 Table 1).
- Conductor areas from Chapter 9 Table 5 (THHN/THWN-2), conduit areas from Table 4.
- Europe: total conductor cross-section ≤ 1/3 of the conduit's inner cross-section.
- More than 3 current-carrying conductors: apply the ampacity adjustment (NEC 310.15(C)(1)).
Frequently asked questions
How many 12 AWG wires in 1/2 inch EMT?
What is the 40 % rule?
Does the ground wire count?
Design aid
For your actual home, move to the editor
Draw your home or describe it to the AI: Circuia places the points, checks the rules in real time and generates the consumer unit, single-line diagram and bill of materials.
Other free tools
- Free toolCable size calculatorPower, length, use → cable size and breaker (mm² or AWG).
- Free toolSockets per roomRoom type + area → minimum sockets, lights, data points.
- Free toolConsumer unit plannerYour home → RCDs, breakers, rows of the panel.
- Free toolSupply capacity calculatorYour appliances → subscription, main fuse or service size.
- Free toolVoltage drop calculatorSize, length, current → % drop, within the limit or not.
- Free toolSingle-line diagram generatorYour home → printable single-line diagram of the panel.