Conduit fill calculator (EMT, PVC, corrugated)

List the conductors: the calculator gives the smallest conduit that holds them — NEC Chapter 9 Table 1 fill with THHN areas for EMT and PVC in the US, and the usual one-third rule for metric corrugated conduits in Europe.

Updated on BS 7671 · NEC

Inputs

Rules applied: BS 7671:2018+A4:2026 — United Kingdom (beta, IET Wiring Regulations 18th Edition) · beta rules, to be checked locally

Single-core conductors (H07V-U/R) in corrugated or smooth conduit.

Conductors
  • ×
  • ×

Result

Minimum conduit

Ø 20mm

Allowed fill

33%

ConduitFill
Ø 16 mm58 %✕
Ø 20 mm33 %✓
Ø 25 mm20 %✓
Ø 32 mm11 %✓
Ø 40 mm7 %✓
Ø 50 mm4 %✓
Ø 63 mm3 %✓

Total conductor area ≤ 1/3 of the conduit's inner area, to pull the wires without damage and leave room to replace them.

Typical catalogue diameters: the manufacturer's figures win.

References

  • § HD 60364-5-52 (522.8)
  • § EN 61386

Estimate for planning only. Switch off before any work and have it checked by a qualified electrician.

Next step · free

Turn this result into a real plan

Draw your rooms, place sockets and lights: Circuia checks every rule as you go and builds the board schedule.

Open the free editor →Free · no sign-up to start
</> Embed this tool on your website

Free, no sign-up. Paste this code into your page (blog, contractor site, forum): the tool shows up and stays up to date.

How it works

  • US: 53 % fill for 1 conductor, 31 % for 2, 40 % for 3 or more (NEC Chapter 9 Table 1).
  • Conductor areas from Chapter 9 Table 5 (THHN/THWN-2), conduit areas from Table 4.
  • Europe: total conductor cross-section ≤ 1/3 of the conduit's inner cross-section.
  • More than 3 current-carrying conductors: apply the ampacity adjustment (NEC 310.15(C)(1)).

Frequently asked questions

How many 12 AWG wires in 1/2 inch EMT?

9 THHN conductors (NEC Annex C, Table C.1), 12 for 14 AWG.

What is the 40 % rule?

With three or more conductors, their total area must not exceed 40 % of the conduit's internal area (NEC Chapter 9 Table 1).

Does the ground wire count?

Yes, equipment grounding conductors count in the fill (Chapter 9 Note 3). Add it to the list.