Bathroom electrical zones: what is allowed where?
Click a zone of the drawing: the tool shows what can be installed there and the IP rating it needs — BS 7671 zones 0, 1 and 2 in the UK, the HD 60364-7-701 zones elsewhere in Europe, and the 3 ft / 8 ft clearances of the NEC in the US.
Updated on BS 7671 · NEC
Result
Zone 1
Above zone 0 up to 2.25 m from the floor.
| Equipment | Allowed? | IP |
|---|---|---|
| Socket outlet | ✕ not allowed | — |
| Shaver socket | ✕ not allowed | — |
| Switch | SELV SELV 12 V only | IPX4 |
| Light fitting | ✓ allowed | IPX4 |
| Extractor fan | ✓ allowed | IPX4 |
| Heated towel rail | ✓ allowed | IPX4 |
| Water heater | ✓ allowed | IPX4 |
| Electric shower / pump | ✓ allowedIPX5 where water jets are used for cleaning. | IPX4 |
| Washing machine | ✕ not allowed | — |
| Under-floor heating | ! under conditionsUnder-floor heating with a metal grid or sheath connected to the protective conductor, 30 mA RCD. | — |
Simplified summary. National deviations and manufacturers' instructions apply; have the bathroom checked by an electrician.
References
- § BS 7671 Section 701 (701.32, 701.512.3)
- § BS 7671 Reg. 701.411.3.3 (30 mA RCD)
Estimate for planning only. Switch off before any work and have it checked by a qualified electrician.
Next step · free
Turn this result into a real plan
Open the editor with a bathroom already drawn: Circuia flags any socket or light placed in the wrong zone.
</> Embed this tool on your website
Free, no sign-up. Paste this code into your page (blog, contractor site, forum): the tool shows up and stays up to date.
How it works
- Zone 0 is inside the bath or shower tray; zone 1 above it up to 2.25 m; zone 2 extends 0.6 m beyond zone 1 (BS 7671 701.32).
- Walk-in showers without a tray: zone 1 extends 1.2 m from the fixed water outlet.
- UK: ordinary sockets at least 3 m from zone 1 (701.512.3); all circuits of the bathroom on a 30 mA RCD (701.411.3.3).
- US: no receptacle within 3 ft horizontally / 8 ft vertically of the tub or shower (406.9(C)); all bathroom receptacles GFCI (210.8(A)(1)).
Frequently asked questions
Can I have a socket in a UK bathroom?
What IP rating for bathroom lights?
How far must a receptacle be from a bathtub in the US?
Design aid
For your actual home, move to the editor
Draw your home or describe it to the AI: Circuia places the points, checks the rules in real time and generates the consumer unit, single-line diagram and bill of materials.
Other free tools
- Free toolCable size calculatorPower, length, use → cable size and breaker (mm² or AWG).
- Free toolSockets per roomRoom type + area → minimum sockets, lights, data points.
- Free toolConsumer unit plannerYour home → RCDs, breakers, rows of the panel.
- Free toolSupply capacity calculatorYour appliances → subscription, main fuse or service size.
- Free toolVoltage drop calculatorSize, length, current → % drop, within the limit or not.
- Free toolSingle-line diagram generatorYour home → printable single-line diagram of the panel.