Residential service load calculator (NEC 220.82 / standard method)
Enter the floor area and the appliances: the calculator runs the NEC dwelling load calculation (optional method 220.82 or the standard method of Article 220 Part III) and gives the load in amps at 240 V and the minimum service size.
Updated on NEC 2023
Result
Calculated load
105A
Minimum service
125A
Exceeds your 100 A service: upgrade, or load management (NEC 625.42 / 750).
NEC 2023 single-family dwelling, 120/240 V. Motors and local amendments not modelled; the permit calculation is the electrician's.
References
- § NEC Article 220 Part III
- § NEC 220.82
- § NEC 230.79(C)
- § NEC 220.87 (existing loads)
Estimate for planning only. Switch off before any work and have it checked by a qualified electrician.
Next step · free
Turn this result into a real plan
Draw your rooms, place sockets and lights: Circuia checks every rule as you go and builds the board schedule.
</> Embed this tool on your website
Free, no sign-up. Paste this code into your page (blog, contractor site, forum): the tool shows up and stays up to date.
How it works
- General lighting 3 VA/ft² (220.41) + 1,500 VA per small-appliance and laundry circuit (220.52).
- Optional method: first 10 kVA at 100 %, the rest at 40 %, plus the largest of heating or cooling (220.82(C)).
- Standard method: Table 220.45 demand factors, fixed appliances at 75 % if 4 or more (220.53), dryer 5 kW min (220.54), range Table 220.55, EVSE at max(7,200 W, nameplate) (220.57).
- Result ÷ 240 V = amps; minimum 100 A service (230.79(C)).
This tool applies US rules (NEC) only.