Residential service load calculator (NEC 220.82 / standard method)

Enter the floor area and the appliances: the calculator runs the NEC dwelling load calculation (optional method 220.82 or the standard method of Article 220 Part III) and gives the load in amps at 240 V and the minimum service size.

Updated on NEC 2023

Inputs

🇺🇸 United States · Rules applied: NFPA 70 NEC 2023

Method
ft²
W
W
W
W
W
W
W
VA
VA
W
W
A

Result

Calculated load

105A

Minimum service

125A

Exceeds your 100 A service: upgrade, or load management (NEC 625.42 / 750).

General loads (§ 220.82(B) — 10 kVA at 100 %, rest at 40 %)20,200 VA
Heating / cooling (§ 220.82(C))5,000 VA
Total25,200 VA ÷ 240 V

NEC 2023 single-family dwelling, 120/240 V. Motors and local amendments not modelled; the permit calculation is the electrician's.

References

  • § NEC Article 220 Part III
  • § NEC 220.82
  • § NEC 230.79(C)
  • § NEC 220.87 (existing loads)

Estimate for planning only. Switch off before any work and have it checked by a qualified electrician.

Next step · free

Turn this result into a real plan

Draw your rooms, place sockets and lights: Circuia checks every rule as you go and builds the board schedule.

Open the free editor →Free · no sign-up to start
</> Embed this tool on your website

Free, no sign-up. Paste this code into your page (blog, contractor site, forum): the tool shows up and stays up to date.

How it works

  • General lighting 3 VA/ft² (220.41) + 1,500 VA per small-appliance and laundry circuit (220.52).
  • Optional method: first 10 kVA at 100 %, the rest at 40 %, plus the largest of heating or cooling (220.82(C)).
  • Standard method: Table 220.45 demand factors, fixed appliances at 75 % if 4 or more (220.53), dryer 5 kW min (220.54), range Table 220.55, EVSE at max(7,200 W, nameplate) (220.57).
  • Result ÷ 240 V = amps; minimum 100 A service (230.79(C)).

This tool applies US rules (NEC) only.

Frequently asked questions

Is a 100 amp service enough?

For a small gas-heated home, often. Electric heat, a heat pump, an electric range and an EV charger together usually need 200 A — the calculation tells you.

Optional or standard method?

The optional method (220.82) usually gives a lower, still code-compliant result for a single dwelling with a 120/240 V service. Both are allowed.

Can I add an EV charger to my existing service?

Run the calculation with the EVSE included; NEC 220.87 also allows using a year of measured demand. An energy management system (625.42) can avoid an upgrade.

Design aid

For your actual home, move to the editor

Draw your home or describe it to the AI: Circuia places the points, checks the rules in real time and generates the consumer unit, single-line diagram and bill of materials.