Receptacle spacing calculator (NEC 210.52 6-ft and 24-in rules)

Enter each wall space between doors and openings: the checker applies NEC 210.52 — no point more than 6 ft from a receptacle along the floor line, no point of a countertop more than 24 in from one — and shows the minimum number and an even layout.

Updated on NEC 2023

Inputs

🇺🇸 United States · Rules applied: NFPA 70 NEC 2023

Wall spaces

Length of each wall space between doors and openings.

  • ft
  • ft
  • ft
  • ft

Result

Minimum receptacles

5

  • Wall space 1 · 12 ft 1

    § NEC 210.52(A)(1)–(2) · 6 ft

  • Wall space 2 · 14 ft 2

    § NEC 210.52(A)(1)–(2) · 3.5 ft · 10.5 ft

  • Wall space 3 · 9 ft 1

    § NEC 210.52(A)(1)–(2) · 4.5 ft

  • Wall space 4 · 6 ft 1

    § NEC 210.52(A)(1)–(2) · 3 ft

  • 120 V 15/20 A circuits in these rooms need AFCI protection (210.12(A)).
  • All 15/20 A dwelling receptacles are tamper-resistant (406.12).

NEC 2023 minimums for dwelling units; local amendments apply. More receptacles are always allowed.

References

  • § NEC 210.52(A)
  • § NEC 210.52(C)
  • § NEC 210.52(D)
  • § NEC 210.52(H)
  • § NEC 406.12 (tamper-resistant)

Estimate for planning only. Switch off before any work and have it checked by a qualified electrician.

Next step · free

Turn this result into a real plan

Open the editor with this room and its receptacles: Circuia checks the 6-ft rule along every wall.

Open the editor with this result →Free · no sign-up to start
</> Embed this tool on your website

Free, no sign-up. Paste this code into your page (blog, contractor site, forum): the tool shows up and stays up to date.

How it works

  • Wall spaces 2 ft or wider need a receptacle; one receptacle covers 6 ft each side (210.52(A)).
  • Countertop spaces 12 in or wider: one receptacle covers 24 in each side (210.52(C)(1)).
  • Islands and peninsulas (2023): 1 for the first 9 ft², +1 per 18 ft² (210.52(C)(2)).
  • Hallways of 10 ft or more: at least one (210.52(H)); bathrooms: one within 3 ft of each basin (210.52(D)).

This tool applies US rules (NEC) only.

Frequently asked questions

What is the 6-ft rule?

No point along the floor line of any wall space may be more than 6 ft from a receptacle (NEC 210.52(A)(1)), so receptacles are at most 12 ft apart.

How many receptacles on a kitchen counter?

Every countertop space 12 in or wider needs one, and no point may be more than 24 in from a receptacle — about one every 4 ft.

Do doors count as wall space?

No: wall space is measured between doorways, fireplaces and similar openings; fixed panels of sliding glass doors do count.

Design aid

For your actual home, move to the editor

Draw your home or describe it to the AI: Circuia places the points, checks the rules in real time and generates the consumer unit, single-line diagram and bill of materials.