Box fill calculator (NEC 314.16)
Count what goes into the box: the calculator applies NEC 314.16(B) — 1 volume per conductor, 2 per device, 1 for all grounds (+¼ beyond four), 1 for clamps — and compares the total with the box volume.
Updated on NEC 2023
Result
Volume needed
16in³
Box volume
14in³
Overfilled: use a larger box, e.g. Device box 3 × 2 × 3-1/2.
NEC 2023 314.16. Local amendments apply; an inspector has the final word.
References
- § NEC 314.16(A)
- § NEC 314.16(B)
- § NEC Table 314.16(A)
- § NEC Table 314.16(B)(1)
Estimate for planning only. Switch off before any work and have it checked by a qualified electrician.
Next step · free
Turn this result into a real plan
Draw your rooms, place sockets and lights: Circuia checks every rule as you go and builds the board schedule.
</> Embed this tool on your website
Free, no sign-up. Paste this code into your page (blog, contractor site, forum): the tool shows up and stays up to date.
How it works
- Volume allowance per conductor from Table 314.16(B)(1): 14 AWG 2.00 in³, 12 AWG 2.25 in³, 10 AWG 2.50 in³.
- Each device yoke counts 2 conductors of the largest size connected to it (314.16(B)(4)).
- All equipment grounding conductors count 1, plus ¼ for each beyond four (314.16(B)(5)).
- Internal clamps count 1 (any number); each fixture stud or hickey counts 1; pigtails inside the box are not counted.
This tool applies US rules (NEC) only.