Standard · Sweden
SS 436 40 00 explained: Sweden's wiring rules for homes (Elinstallationsreglerna)
SS 436 40 00, the Swedish Electrical Installation Rules (Elinstallationsreglerna), is the standard used to show that a home's wiring meets the Electrical Safety Act (elsäkerhetslagen). The current text is edition 4 (2023) with amendment R1:2024. Fixed installation work must be done by an authorised electrician (auktoriserad elinstallatör), who checks and documents it through self-inspection (egenkontroll).
Updated on Last checked SS 436 40 00 · beta
Key facts
- 01The Electrical Safety Act (2016:732) and Elsäkerhetsverket's regulations ELSÄK-FS 2022:1 to 2022:3 (in force since 1 December 2022) require “good electrical safety practice”, presumed met by SS 436 40 00.
- 02SS 436 40 00 edition 4 was adopted on 8 May 2023, with amendment R1:2024; SEK Handbok 444 is the commented version.
- 0330 mA RCDs protect socket-outlets up to 32 A and lighting in dwellings.
- 04Swedish practice protects 1.5 mm² circuits at 10 A and 2.5 mm² at 16 A, lower than the 16 A / 20 A often used elsewhere in Europe.
- 05Houses (villor) are normally supplied three-phase 3 × 400 V with main fuses of 16, 20 or 25 A.
What is SS 436 40 00 and is it mandatory?
SS 436 40 00, “Elinstallationer för lågspänning”, is published by the Swedish standards bodies (SIS, prepared by SEK Svensk Elstandard). It is the Swedish edition of the international HD 60364 series, with a small number of national deviations. Electricians usually work from SEK Handbok 444, which contains the standard with comments.
The legal framework changed on 1 December 2022. Elsäkerhetsverket's new regulations (ELSÄK-FS 2022:1, 2022:2 and 2022:3, under the Electrical Safety Act 2016:732) no longer contain detailed technical rules. They require installations to follow good electrical safety practice (god elsäkerhetsteknisk praxis), and an installation built to SS 436 40 00 is presumed to meet that requirement. In other words, the standard is not law, but it is the practical reference every authorised electrician works to.
| Text | What it covers | Status |
|---|---|---|
| Elsäkerhetslagen (2016:732) | Electrical Safety Act: who may do electrical installation work | Law |
| ELSÄK-FS 2022:1–3 | Elsäkerhetsverket regulations (authorisation, installations, egenkontroll) | Binding since 1 December 2022 |
| SS 436 40 00 utg 4:2023 + R1:2024 | Technical rules for low-voltage installations | Presumption of conformity |
| SEK Handbok 444 | Commented edition of SS 436 40 00 | Guidance |
| SS 437 01 02 utg 2:2018 | Recommended minimum socket equipment in homes | Contractual guide, not binding |
Who may do the work: auktoriserad elinstallatör and egenkontroll
In Sweden, electrical installation work must be carried out by, or under the supervision of, an authorised electrician (auktoriserad elinstallatör), working for a company that has a self-inspection programme (egenkontrollprogram). Elsäkerhetsverket issues three types of authorisation today; the older “behörighet” classes (AB, B, A, D) were converted.
| Authorisation | Scope |
|---|---|
| A (auktorisation A) | All electrical installation work |
| AL | Work on low-voltage installations |
| B | Limited: work in existing final circuits |
There is no third-party inspection of a new home installation. The electrician inspects and tests the work (SS 436 40 00 part 6) and records it in the company's egenkontroll. The grid owner (nätägare) is notified before the work with a föranmälan (advance notice) and afterwards with a färdiganmälan (completion notice).
Supply: three-phase 3 × 400 V and main fuses
Swedish houses are normally connected three-phase, 3 × 400 V (230 V between each phase and neutral). The size of the connection is set by the main fuses (huvudsäkringar) in the grid owner's meter cabinet. Circuits are spread over the three phases, and large loads such as a cooker, an EV charger or a heat pump are often three-phase. The earthing arrangement is assumed to be TN-C-S in the Circuia pack, a value we have not confirmed from a public source.
| Main fuse | Approximate power (√3 × 400 V × I) |
|---|---|
| 16 A | 11.1 kW |
| 20 A | 13.9 kW |
| 25 A | 17.3 kW |
Circuits and protective devices: why 10 A on 1.5 mm²
The most visible Swedish habit is the 10 A breaker on 1.5 mm² cable, used for lighting and ordinary socket circuits, with 16 A reserved for 2.5 mm² circuits in kitchens and for appliances. The reason is cable capacity: 1.5 mm² copper in conduit in a wall (the common Swedish method) carries about 13.5 A, while the same cable clipped to the surface carries about 17.5 A. A 16 A breaker on 1.5 mm² is possible only for some installation methods.
| Copper section | Largest breaker | Typical use | Status |
|---|---|---|---|
| 1.5 mm² | 10 A | Lighting, ordinary sockets, outdoor sockets | Swedish practice (16 A only for some installation methods) |
| 2.5 mm² | 16 A | Kitchen worktop sockets, washing machine, dishwasher, water heater | Swedish practice |
| 4 mm² | 25 A | Heating, larger loads | European base value |
| 6 mm² | 32 A | EV charger, heat pump | European base value |
| 10 mm² | 40 A | Sub-boards | European base value |
- Cooker (spis): Circuia proposes a three-phase 16 A circuit by default. This is common practice, but we have not found a public source confirming it.
- Sockets per circuit: no Swedish maximum was found. Circuia plans about eight per circuit and informs above ten.
- EV charging: a dedicated circuit with its own 30 mA RCD (type A with 6 mA DC detection, or type B), as in the European base. Three-phase charging at 11 kW is common on a 3 × 400 V supply.
- Surge protection (överspänningsskydd) follows the risk assessment of section 443: typically needed with an overhead line or a lightning protection system, not unconditionally required.
RCDs (jordfelsbrytare): what needs 30 mA protection
SS 436 40 00 requires additional protection by a 30 mA RCD for socket-outlets up to 32 A used by ordinary persons (411.3.3). The former regulation limited to 16 A sockets (ELSÄK-FS 2008:1) has disappeared from Elsäkerhetsverket's rules, but the requirement remains in the standard. Since edition 3 (2017), lighting circuits in dwellings also need 30 mA protection. Bathroom circuits and EV charging points are covered too.
No Swedish limit on the number of circuits per RCD was found. Circuia uses at least 2 type A RCDs with about six circuits each, so a single fault does not leave the whole home without power, and a separate RCD for each EV charger.
Bathrooms: the zone system
No Swedish deviation from the harmonised bathroom rules (HD 60364-7-701) was found in public sources, so the Circuia pack applies the European zones.
| Zone | Extent | What is allowed |
|---|---|---|
| 0 | Inside the bath or shower tray | Only equipment designed for it (SELV) |
| 1 | Above the bath or shower up to 2.25 m | Fixed equipment suitable for the zone (IPX4 minimum) |
| 2 | 0.6 m beyond zone 1 | No ordinary sockets or switches |
| Outside the zones | — | Sockets allowed, behind a 30 mA RCD |
How many sockets? SS 437 01 02 (guide, not law)
Sweden has no binding minimum of sockets per room. The standard SS 437 01 02 (edition 2, 2018) gives recommended equipment levels that are often written into building contracts. According to secondary sources, it counts one socket point per 3.75 m of usable wall length, rounded up (the divisor was 4 m before 2014). A bedroom with 12 m of usable wall would get 4 socket points.
Whether a double socket counts as one or two points, and the exact per-room values, are in the paid standard and not confirmed here. Circuia shows this guide as information only, never as an error, and keeps about 20 % spare space in the consumer unit as practice.
Planning an SS 436 40 00 installation with Circuia
Choose Sweden when you create the project. The editor spreads circuits over three phases, uses 10 A on 1.5 mm² for lighting and ordinary sockets and 16 A on 2.5 mm² for the kitchen and appliances, puts sockets and lighting behind 30 mA type A RCDs, checks the bathroom zones and shows the SS 437 01 02 socket guide as information. It prepares a circuit list, single-line diagram, bill of materials and an egenkontroll checklist for your electrician.
Open the editor set up for Sweden (free, in your browser). Neighbouring countries: Norway, Denmark, Finland, or the overview of all standards.
Common mistakes
- Protecting 1.5 mm² cable in conduit at 16 A: Swedish practice is 10 A.
- Leaving lighting circuits in a dwelling without 30 mA RCD protection (required since edition 3, 2017).
- Putting the whole home on a single RCD.
- Treating SS 437 01 02 socket numbers as a legal minimum: it is a contractual guide.
- Starting fixed wiring work without an authorised electrician and egenkontroll.
- Forgetting the föranmälan and färdiganmälan to the grid owner.
Frequently asked questions
What is the current edition of SS 436 40 00?
Is SS 436 40 00 a legal requirement in Sweden?
Can I do my own electrical installation work in Sweden?
Why are Swedish socket circuits often 10 A?
Do lighting circuits need an RCD in Sweden?
Does Circuia certify an installation to SS 436 40 00?
Design aid
Design the installation with this country's rules
Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.
Written by
Circuia team
Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.
Published · updated
Sources
Sources used for this page, official texts first:
- SIS — SS 436 40 00 utg 4:2023 + R1:2024
- Elsäkerhetsverket — when is an RCD required (jordfelsbrytare)
- Elsäkerhetsverket — authorisation types
- Elsäkerhetsverket — what is authorisation
- elinstallatoren.se — the ELSÄK-FS 2022 regulations (11/2022)
- SEK — revised SS 437 01 02
- voltimum.se — SS 437 01 02 (wall length / 3.75 m)
- elinstallation.nu — cable section and fuse for 1.5 mm²
- elinstallation.nu — main fuses 16 / 20 / 25 A
Related pages
- OverviewElectrical wiring standards in Europe, country by countryHome wiring rules explained for the UK (BS 7671), Ireland (I.S. 10101), Norway, Sweden, Denmark and Finland, with the Circuia editor for each country.
- GuideNEK 400:2026 explained: Norway's wiring rules for homes, IT network includedNEK 400:2026 for Norwegian homes: the 230 V IT network, one RCD per circuit, stove guards, socket minimums, 30 % spare space and the samsvarserklæring.
- GuideDanish wiring rules explained: DS/HD 60364 and the installation order BEK 1082Denmark's wiring rules for homes: BEK 1082 and DS/HD 60364, TT earthing, 30 mA type A RCDs, 13 A sockets, one socket per 4 m² and authorised electricians.
- GuideSFS 6000 explained: Finland's wiring rules for homes (SFS 6000:2022)SFS 6000:2022 for homes in Finland: Tukes and registered contractors, type A 30 mA RCDs, 10 A on 1.5 mm², 3 × 25 A supply and the commissioning inspection.
- CircuiaPricing: free, Project Pass €39, Pro €49/monthCircuia plans: Free to explore, Project Pass at €39 incl. VAT for a homeowner project, Pro at €49 excl. VAT/month and Team at €129 excl. VAT/month for electricians. 14-day trial.
- CircuiaCircuia: AI wiring plans to BS 7671 and EU standardsDraw your home or ask the AI: Circuia designs circuits and the consumer unit, checked against BS 7671, I.S. 10101 and the rules of 17 European countries.