SS 436 40 00 explained: Sweden's wiring rules for homes (Elinstallationsreglerna)

SS 436 40 00, the Swedish Electrical Installation Rules (Elinstallationsreglerna), is the standard used to show that a home's wiring meets the Electrical Safety Act (elsäkerhetslagen). The current text is edition 4 (2023) with amendment R1:2024. Fixed installation work must be done by an authorised electrician (auktoriserad elinstallatör), who checks and documents it through self-inspection (egenkontroll).

Updated on Last checked SS 436 40 00 · beta

Key facts

  • 01The Electrical Safety Act (2016:732) and Elsäkerhetsverket's regulations ELSÄK-FS 2022:1 to 2022:3 (in force since 1 December 2022) require “good electrical safety practice”, presumed met by SS 436 40 00.
  • 02SS 436 40 00 edition 4 was adopted on 8 May 2023, with amendment R1:2024; SEK Handbok 444 is the commented version.
  • 0330 mA RCDs protect socket-outlets up to 32 A and lighting in dwellings.
  • 04Swedish practice protects 1.5 mm² circuits at 10 A and 2.5 mm² at 16 A, lower than the 16 A / 20 A often used elsewhere in Europe.
  • 05Houses (villor) are normally supplied three-phase 3 × 400 V with main fuses of 16, 20 or 25 A.

What is SS 436 40 00 and is it mandatory?

SS 436 40 00, “Elinstallationer för lågspänning”, is published by the Swedish standards bodies (SIS, prepared by SEK Svensk Elstandard). It is the Swedish edition of the international HD 60364 series, with a small number of national deviations. Electricians usually work from SEK Handbok 444, which contains the standard with comments.

The legal framework changed on 1 December 2022. Elsäkerhetsverket's new regulations (ELSÄK-FS 2022:1, 2022:2 and 2022:3, under the Electrical Safety Act 2016:732) no longer contain detailed technical rules. They require installations to follow good electrical safety practice (god elsäkerhetsteknisk praxis), and an installation built to SS 436 40 00 is presumed to meet that requirement. In other words, the standard is not law, but it is the practical reference every authorised electrician works to.

Swedish texts that apply to home wiring
TextWhat it coversStatus
Elsäkerhetslagen (2016:732)Electrical Safety Act: who may do electrical installation workLaw
ELSÄK-FS 2022:1–3Elsäkerhetsverket regulations (authorisation, installations, egenkontroll)Binding since 1 December 2022
SS 436 40 00 utg 4:2023 + R1:2024Technical rules for low-voltage installationsPresumption of conformity
SEK Handbok 444Commented edition of SS 436 40 00Guidance
SS 437 01 02 utg 2:2018Recommended minimum socket equipment in homesContractual guide, not binding
Sources: Elsäkerhetsverket, SIS, elinstallatoren.se (11/2022), SEK.

Who may do the work: auktoriserad elinstallatör and egenkontroll

In Sweden, electrical installation work must be carried out by, or under the supervision of, an authorised electrician (auktoriserad elinstallatör), working for a company that has a self-inspection programme (egenkontrollprogram). Elsäkerhetsverket issues three types of authorisation today; the older “behörighet” classes (AB, B, A, D) were converted.

Electrician authorisation in Sweden (Elsäkerhetsverket)
AuthorisationScope
A (auktorisation A)All electrical installation work
ALWork on low-voltage installations
BLimited: work in existing final circuits
Source: Elsäkerhetsverket, authorisation types. Check the exact scope of each type on elsakerhetsverket.se before hiring.

There is no third-party inspection of a new home installation. The electrician inspects and tests the work (SS 436 40 00 part 6) and records it in the company's egenkontroll. The grid owner (nätägare) is notified before the work with a föranmälan (advance notice) and afterwards with a färdiganmälan (completion notice).

Supply: three-phase 3 × 400 V and main fuses

Swedish houses are normally connected three-phase, 3 × 400 V (230 V between each phase and neutral). The size of the connection is set by the main fuses (huvudsäkringar) in the grid owner's meter cabinet. Circuits are spread over the three phases, and large loads such as a cooker, an EV charger or a heat pump are often three-phase. The earthing arrangement is assumed to be TN-C-S in the Circuia pack, a value we have not confirmed from a public source.

Typical main fuses of a Swedish house (3 × 400 V)
Main fuseApproximate power (√3 × 400 V × I)
16 A11.1 kW
20 A13.9 kW
25 A17.3 kW
Source: elinstallation.nu (main fuses 16, 20 and 25 A). Power is a calculation, not a guaranteed capacity.

Circuits and protective devices: why 10 A on 1.5 mm²

The most visible Swedish habit is the 10 A breaker on 1.5 mm² cable, used for lighting and ordinary socket circuits, with 16 A reserved for 2.5 mm² circuits in kitchens and for appliances. The reason is cable capacity: 1.5 mm² copper in conduit in a wall (the common Swedish method) carries about 13.5 A, while the same cable clipped to the surface carries about 17.5 A. A 16 A breaker on 1.5 mm² is possible only for some installation methods.

Largest breaker per cable size in the Circuia Sweden pack
Copper sectionLargest breakerTypical useStatus
1.5 mm²10 ALighting, ordinary sockets, outdoor socketsSwedish practice (16 A only for some installation methods)
2.5 mm²16 AKitchen worktop sockets, washing machine, dishwasher, water heaterSwedish practice
4 mm²25 AHeating, larger loadsEuropean base value
6 mm²32 AEV charger, heat pumpEuropean base value
10 mm²40 ASub-boardsEuropean base value
Source: elinstallation.nu (1.5 mm² → 10 A practice, Iz ≈ 13.5 A in conduit per table 52B.2). The formal limits in SEK Handbok 444 were not read.
  • Cooker (spis): Circuia proposes a three-phase 16 A circuit by default. This is common practice, but we have not found a public source confirming it.
  • Sockets per circuit: no Swedish maximum was found. Circuia plans about eight per circuit and informs above ten.
  • EV charging: a dedicated circuit with its own 30 mA RCD (type A with 6 mA DC detection, or type B), as in the European base. Three-phase charging at 11 kW is common on a 3 × 400 V supply.
  • Surge protection (överspänningsskydd) follows the risk assessment of section 443: typically needed with an overhead line or a lightning protection system, not unconditionally required.

RCDs (jordfelsbrytare): what needs 30 mA protection

SS 436 40 00 requires additional protection by a 30 mA RCD for socket-outlets up to 32 A used by ordinary persons (411.3.3). The former regulation limited to 16 A sockets (ELSÄK-FS 2008:1) has disappeared from Elsäkerhetsverket's rules, but the requirement remains in the standard. Since edition 3 (2017), lighting circuits in dwellings also need 30 mA protection. Bathroom circuits and EV charging points are covered too.

No Swedish limit on the number of circuits per RCD was found. Circuia uses at least 2 type A RCDs with about six circuits each, so a single fault does not leave the whole home without power, and a separate RCD for each EV charger.

Bathrooms: the zone system

No Swedish deviation from the harmonised bathroom rules (HD 60364-7-701) was found in public sources, so the Circuia pack applies the European zones.

Bathroom zones applied for Sweden (HD 60364-7-701)
ZoneExtentWhat is allowed
0Inside the bath or shower trayOnly equipment designed for it (SELV)
1Above the bath or shower up to 2.25 mFixed equipment suitable for the zone (IPX4 minimum)
20.6 m beyond zone 1No ordinary sockets or switches
Outside the zonesSockets allowed, behind a 30 mA RCD
Every bathroom circuit is protected by a 30 mA RCD. Check SEK Handbok 444 for any Swedish detail not covered by public sources.

How many sockets? SS 437 01 02 (guide, not law)

Sweden has no binding minimum of sockets per room. The standard SS 437 01 02 (edition 2, 2018) gives recommended equipment levels that are often written into building contracts. According to secondary sources, it counts one socket point per 3.75 m of usable wall length, rounded up (the divisor was 4 m before 2014). A bedroom with 12 m of usable wall would get 4 socket points.

Whether a double socket counts as one or two points, and the exact per-room values, are in the paid standard and not confirmed here. Circuia shows this guide as information only, never as an error, and keeps about 20 % spare space in the consumer unit as practice.

Planning an SS 436 40 00 installation with Circuia

Choose Sweden when you create the project. The editor spreads circuits over three phases, uses 10 A on 1.5 mm² for lighting and ordinary sockets and 16 A on 2.5 mm² for the kitchen and appliances, puts sockets and lighting behind 30 mA type A RCDs, checks the bathroom zones and shows the SS 437 01 02 socket guide as information. It prepares a circuit list, single-line diagram, bill of materials and an egenkontroll checklist for your electrician.

Open the editor set up for Sweden (free, in your browser). Neighbouring countries: Norway, Denmark, Finland, or the overview of all standards.

Common mistakes

  • Protecting 1.5 mm² cable in conduit at 16 A: Swedish practice is 10 A.
  • Leaving lighting circuits in a dwelling without 30 mA RCD protection (required since edition 3, 2017).
  • Putting the whole home on a single RCD.
  • Treating SS 437 01 02 socket numbers as a legal minimum: it is a contractual guide.
  • Starting fixed wiring work without an authorised electrician and egenkontroll.
  • Forgetting the föranmälan and färdiganmälan to the grid owner.

Frequently asked questions

What is the current edition of SS 436 40 00?

Edition 4, SS 436 40 00 utg 4:2023, adopted on 8 May 2023, with amendment R1:2024. SEK Handbok 444 is the commented edition electricians usually use. Since 1 December 2022, Elsäkerhetsverket's regulations ELSÄK-FS 2022:1 to 2022:3 refer to good electrical safety practice, which SS 436 40 00 is presumed to meet.

Is SS 436 40 00 a legal requirement in Sweden?

Not directly. The Electrical Safety Act (2016:732) and the ELSÄK-FS 2022 regulations require good electrical safety practice. Following SS 436 40 00 is the recognised way to meet that requirement, so authorised electricians design and check home installations against it.

Can I do my own electrical installation work in Sweden?

Fixed electrical installation work must be done by an authorised electrician (auktoriserad elinstallatör) working under a company's self-inspection programme (egenkontrollprogram). Authorisation types today are A, AL and B, with B limited to work in existing final circuits. Check Elsäkerhetsverket's guidance before touching any fixed wiring.

Why are Swedish socket circuits often 10 A?

Because ordinary socket and lighting circuits are commonly wired in 1.5 mm² cable in conduit, which carries about 13.5 A. A 10 A breaker protects it safely; 16 A is used on 2.5 mm² circuits for the kitchen and appliances, or on 1.5 mm² only where the installation method allows it.

Do lighting circuits need an RCD in Sweden?

Yes, in dwellings. Since edition 3 of SS 436 40 00 (2017), lighting circuits in homes need 30 mA additional protection, in addition to socket-outlets up to 32 A, bathroom circuits and EV charging points. Circuia puts them behind type A RCDs shared between several circuits, never a single RCD for the whole home.

Does Circuia certify an installation to SS 436 40 00?

No. Circuia checks a plan against its Sweden rules pack, which is in beta and built from public sources, and produces the circuit list, single-line diagram, bill of materials and an egenkontroll checklist. Only an authorised electrician can carry out, test and document the installation.

Design aid

Design the installation with this country's rules

Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.

Open the editor for this country

Written by

Circuia team

Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.