Standard · Denmark
Danish wiring rules explained: DS/HD 60364 and the installation order BEK 1082
In Denmark, home wiring follows the installation order BEK 1082 (elinstallationsbekendtgørelsen, in force since 1 July 2017) and the DS/HD 60364 standards it refers to. It sets numeric rules: 30 mA type A RCDs on practically every circuit, type AC RCDs banned, sockets protected at 13 A, one socket per started 4 m² of each room, and work by an authorised electrical contractor.
Updated on Last checked DS/HD 60364 + BEK 1082 · beta
Key facts
- 01BEK nr 1082 of 12 July 2016, amended by BEK 639/2017, has applied since 1 July 2017 and is still valid in 2026; the applicable DS/HD 60364 parts are listed in the Standardsamling, 10th edition (2025).
- 02New installations need 30 mA RCDs on household sockets up to 20 A and every other connection point protected at up to 32 A (§ 35); type AC is banned in dwellings (§ 53).
- 0310 A and 13 A sockets are protected at 13 A maximum (§ 45).
- 04Each room needs 1 socket per started 4 m², up to 10 required; the kitchen at least 3 sockets on 2 circuits (§ 57).
- 05A home needs at least one socket or lighting circuit per 50 m² of floor area, minimum 2 (§ 56).
- 06TT is the default earthing system for new installations (§ 27).
Which rules apply to electrical installations in Denmark?
Denmark regulates installations through an executive order rather than a national wiring standard. The installation order (installationsbekendtgørelsen, BEK nr 1082 of 12 July 2016, amended by BEK 639/2017) makes the harmonised DS/HD 60364 series mandatory and adds Danish requirements in its own paragraphs. The authority is the Danish Safety Technology Authority (Sikkerhedsstyrelsen).
The older Heavy Current Regulations (stærkstrømsbekendtgørelsen, sections 6, 6A, 6B and 8) were repealed on 1 July 2019 and only matter for existing installations built under them. The parts of DS/HD 60364 that apply are collected in the standards collection (Standardsamling til installationsbekendtgørelsen), whose 10th edition dates from 2025.
| Text | What it covers | Status |
|---|---|---|
| BEK 1082/2016 (+ BEK 639/2017) | Installation order: Danish requirements, reference to DS/HD 60364 | Mandatory since 1 July 2017 |
| Standardsamling, 10th edition (2025) | The DS/HD 60364 parts that apply | Mandatory by reference |
| Authorisation Act (LBK 30/2019) + BEK 722/2024 | Authorisation of electrical contractors | Mandatory |
| BEK 725/2024 | Quality management system of authorised companies | Mandatory |
| Stærkstrømsbekendtgørelsen 6 / 6A / 6B / 8 | Previous rules | Repealed 1 July 2019 |
Supply and earthing: three-phase and TT by default
Danish houses are supplied three-phase 3 × 400/230 V; a main fuse of 3 × 25 A is typical, with 35 A as an option (Trefor). Under § 27 and § 28 of BEK 1082 the default earthing system is TT, with the home's own earth electrode. A TN system is only allowed in listed cases: a customer's own transformer, a cable direct from the substation, an existing TN installation, or the grid owner's permission. TN-C is not allowed after the first distribution board.
Because TT relies on RCDs to disconnect earth faults, the Danish RCD rules below are central to the whole design.
RCDs, the 13 A socket rule and circuit sizes
| Rule | Value | Paragraph |
|---|---|---|
| 30 mA RCD on household sockets | Sockets up to 20 A | § 35 |
| 30 mA RCD on other connection points | Protected at up to 32 A: in practice every final circuit, lighting included | § 35 |
| RCD type in dwellings | Type A minimum, type AC banned | § 53 |
| 10 A and 13 A socket-outlets | Short-circuit protection at 13 A maximum | § 45 |
| 16 A socket-outlets | Protection at 16 A maximum | § 45 |
| Earth contact for class I appliances | Required in homes built after 1 July 2017 | § 54 |
| Existing installations | RCD on sockets up to 16 A and other points up to 20 A | § 61 |
The 13 A limit follows from the Danish socket system: household sockets are the Danish type K (DS 60884-2-D1), rated 10 or 13 A. A standard socket circuit is therefore a 13 A circuit, not the 16 A or 20 A common elsewhere in Europe.
| Copper section | Largest breaker | Typical use | Status |
|---|---|---|---|
| 1.5 mm² | 13 A | Socket and lighting circuits | Consistent with the 13 A socket rule; section of socket circuits not confirmed |
| 2.5 mm² | 20 A | Appliances, water heater | European base value |
| 4 mm² | 25 A | Heating, larger loads | European base value |
| 6 mm² | 32 A | EV charger, heat pump | European base value |
- Surge protection (overspændingsbeskyttelse) is required unless a risk assessment shows it is not needed, or the installation of a single-family house is worth less than five times the cost of the SPD. It is considered mandatory with an EV charger.
- EV charging: its own circuit and its own RCD, type A 30 mA with 6 mA DC detection, or type B (DS/HD 60364-7-722, Sikkerhedsstyrelsen).
- Ceiling light points use fixed terminals, a DCL connector (EN 61995-2) or a Danish plug (§ 58).
How many sockets and circuits does a Danish home need?
BEK 1082 is one of the few European texts that fixes the number of sockets and circuits in a home. The minimums apply to new dwellings.
| Space | Minimum | Paragraph |
|---|---|---|
| Each room | 1 socket per started 4 m² of floor, at most 10 required | § 57 stk. 1 |
| Kitchen area | 3 sockets, spread over at least 2 circuits | § 57 stk. 2 |
| Kitchenette | 1 socket | § 57 stk. 3 |
| Bathroom, WC | 1 socket, unless the room is too small to place it safely (the 4 m² rule does not apply) | § 57 stk. 4 |
| Garage, carport, attic, storage room | No minimum | § 57 stk. 5 |
| Whole dwelling | Socket and lighting circuits ≥ floor area / 50 m², at least 2 | § 56 |
Examples: a 13 m² bedroom needs 4 sockets, a 30 m² living room 8, and a 45 m² open-plan room hits the cap of 10. A 140 m² house needs at least 3 socket and lighting circuits, a 60 m² flat at least 2.
Bathrooms and the consumer unit
| Zone | Extent | Rule |
|---|---|---|
| 0 | Inside the bath or shower tray | Only equipment designed for it |
| 1 | Above the bath or shower up to 2.25 m | Fixed equipment suitable for the zone |
| 2 | 0.6 m beyond zone 1 | No ordinary sockets or switches |
| Room | — | At least 1 socket outside the zones where there is space; every circuit behind a 30 mA RCD |
- The consumer unit (gruppetavle) must be inside the dwelling and at most 2.2 m above the floor (§ 55).
- If it is less than 1 m above the floor, it must be in a lockable cabinet.
Authorised electricians, verification and Sikkerhedsstyrelsen
Fixed electrical installation work in Denmark is carried out by an authorised electrical contractor (autoriseret elinstallatør) under the Authorisation Act, working within a certified quality management system. There is no systematic third-party inspection of a new home.
- Before energising (§ 75), the contractor inspects and tests the installation and draws up a report in line with DS/HD 60364-6.
- Deviations (§ 84): if the contractor does not follow DS/HD 60364, or follows it only partly, they must notify Sikkerhedsstyrelsen within 14 days, with documentation, calculations and drawings.
- The owner receives the documentation of inspection and testing, the circuit list and the plans.
Planning a Danish installation with Circuia
Choose Denmark when you create the project. The editor uses TT earthing and a three-phase supply, protects type K socket circuits at 13 A, puts every final circuit up to 32 A behind 30 mA type A RCDs, flags any type AC device as an error, counts the § 57 socket minimums room by room, checks the § 56 circuit count and the kitchen rule, and reminds you of the § 55 board position. The circuit list, single-line diagram and bill of materials follow.
Open the editor set up for Denmark (free, in your browser). Neighbouring countries: Norway, Sweden, Finland, or the overview of all standards.
Common mistakes
- Fitting type AC RCDs in a dwelling: BEK 1082 § 53 requires type A as a minimum.
- Protecting 13 A type K socket circuits at 16 A instead of 13 A.
- Leaving lighting circuits without an RCD: every connection point protected at up to 32 A needs one.
- Counting sockets per home instead of per room (1 per started 4 m² in each room).
- Putting all kitchen sockets on one circuit: at least 3 sockets on 2 circuits.
- Mounting the consumer unit higher than 2.2 m, or outside the dwelling.
Frequently asked questions
Which standard applies to electrical installations in Denmark?
Are type AC RCDs allowed in Denmark?
How many sockets does a room need in Denmark?
Why are Danish socket circuits protected at 13 A?
Can I do my own electrical work in Denmark?
Does Circuia certify an installation to Danish rules?
Design aid
Design the installation with this country's rules
Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.
Written by
Circuia team
Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.
Published · updated
Sources
Sources used for this page, official texts first:
Related pages
- OverviewElectrical wiring standards in Europe, country by countryHome wiring rules explained for the UK (BS 7671), Ireland (I.S. 10101), Norway, Sweden, Denmark and Finland, with the Circuia editor for each country.
- GuideNEK 400:2026 explained: Norway's wiring rules for homes, IT network includedNEK 400:2026 for Norwegian homes: the 230 V IT network, one RCD per circuit, stove guards, socket minimums, 30 % spare space and the samsvarserklæring.
- GuideSS 436 40 00 explained: Sweden's wiring rules for homes (Elinstallationsreglerna)SS 436 40 00 edition 4 for Swedish homes: elsäkerhetslagen, authorised electricians, 30 mA RCDs, 10 A on 1.5 mm², three-phase supply and egenkontroll.
- GuideSFS 6000 explained: Finland's wiring rules for homes (SFS 6000:2022)SFS 6000:2022 for homes in Finland: Tukes and registered contractors, type A 30 mA RCDs, 10 A on 1.5 mm², 3 × 25 A supply and the commissioning inspection.
- CircuiaPricing: free, Project Pass €39, Pro €49/monthCircuia plans: Free to explore, Project Pass at €39 incl. VAT for a homeowner project, Pro at €49 excl. VAT/month and Team at €129 excl. VAT/month for electricians. 14-day trial.
- CircuiaCircuia: AI wiring plans to BS 7671 and EU standardsDraw your home or ask the AI: Circuia designs circuits and the consumer unit, checked against BS 7671, I.S. 10101 and the rules of 17 European countries.