SFS 6000 explained: Finland's wiring rules for homes (SFS 6000:2022)
SFS 6000 is the Finnish standard for low-voltage electrical installations, and the current edition, SFS 6000:2022, has been applied since 2023. For a home it requires type A 30 mA RCDs on sockets and lighting, and every job ends with a commissioning inspection (käyttöönottotarkastus). Installation work is done by an electrical contractor, under the supervision of Tukes.
Updated on Last checked SFS 6000:2022 · beta
Key facts
- 01The Electrical Safety Act 1135/2016 (sähköturvallisuuslaki) is the legal basis; SFS 6000:2022 is the standard that shows compliance, applied since 2023.
- 02Since SFS 6000-4-41:2017 (applied from 2018), type A 30 mA RCDs protect socket-outlets up to 32 A and the lighting of dwellings and their outdoor areas.
- 03Finnish practice protects 1.5 mm² circuits at 10 A and 2.5 mm² at 16 A.
- 04A house is typically supplied 3 × 400 V with a 3 × 25 A main fuse.
- 05A commissioning inspection is required for every job; a third-party verification inspection is needed for residential buildings with more than 2 dwellings or a main fuse above 35 A.
What is SFS 6000 and how does it relate to Finnish law?
SFS 6000, “Pienjännitesähköasennukset” (low-voltage electrical installations), is the Finnish edition of the harmonised HD 60364 series, prepared by SESKO, the Finnish electrotechnical standards association, with Finnish national deviations. The current edition is SFS 6000:2022, applied since 2023.
The legal framework is the Electrical Safety Act 1135/2016. The Finnish Safety and Chemicals Agency (Tukes) supervises electrical safety and the contractors who carry out installation work. Following SFS 6000 is the recognised way for a contractor to show that an installation meets the Act's safety requirements.
According to SESKO, the 2022 revision changed relatively little for homes compared with SFS 6000:2017: the exceptions to RCD protection in part 4-41 were clarified, the fire-reaction class Dca became partly mandatory for cables, the EV charging part 7-722 was updated and the scope of the bathroom part 7-701 changed. According to STUL, new unearthed sockets may no longer be added to old installations, and arc fault detection devices (AFDD) are recommended in timber buildings and on bedroom socket circuits.
Supply: 3 × 400 V and a 3 × 25 A main fuse
Finnish houses are normally connected three-phase, 3 × 400 V (230 V between phase and neutral), with a main fuse of 3 × 25 A as the typical size. Circuits are spread over the three phases and large loads, such as a sauna heater, a cooker or an EV charger, are often three-phase. The Circuia pack assumes TN-C-S earthing and a three-phase 16 A cooker circuit; both are usual defaults that we have not confirmed from a public Finnish source.
RCDs (vikavirtasuoja) and circuit sizes
| Rule | Value | Source / confidence |
|---|---|---|
| RCD on socket-outlets up to 32 A | Type A, 30 mA | SFS 6000-4-41:2017, SESKO (high) |
| RCD on lighting | Type A, 30 mA, for dwellings and their outdoor areas | SFS 6000-4-41:2017 (high / medium) |
| RCD type AC | Not accepted where type A is required | SESKO |
| Exception to RCD protection | Reportedly only the socket of a fridge or freezer (SFS 6000:2022) | Secondary source, not confirmed |
| Leakage current per RCD | Sum of leakage at most 1/3 of IΔn (10 mA for a 30 mA RCD) | SKT-säätiö (medium) |
| AFDD | Recommended in timber buildings and on bedroom socket circuits | STUL (medium) |
| EV charging | Own RCD, type B or type A with 6 mA DC detection | SESKO (high) |
| Copper section | Largest breaker | Typical use | Status |
|---|---|---|---|
| 1.5 mm² | 10 A | Lighting, ordinary sockets | Finnish practice (Iz about 13.5 A in wall conduit); low to medium confidence |
| 2.5 mm² | 16 A | Kitchen sockets, appliances, cooker (three-phase) | Finnish practice |
| 4 mm² | 25 A | Heating, sauna heater, larger loads | European base value |
| 6 mm² | 32 A | EV charger, heat pump | European base value |
| 10 mm² | 40 A | Sub-boards | European base value |
Surge protection (ylijännitesuoja) is required mainly for houses supplied by an overhead line; otherwise it follows a risk assessment, and Finland has a national condition reflecting its low number of thunderstorm days. Circuia reminds you of this assessment whenever no SPD is planned. No Finnish limit on the number of sockets per circuit was found.
Bathrooms and saunas: the zone system
Finnish bathrooms follow SFS 6000-7-701, the national edition of the harmonised bathroom part. Its scope changed in 2022; the details were not available in public sources, so Circuia applies the harmonised zones and every bathroom circuit is behind a 30 mA RCD. Saunas are covered by a separate part (7-703) that the Circuia pack does not check.
| Zone | Extent | Rule |
|---|---|---|
| 0 | Inside the bath or shower tray | Only equipment designed for it |
| 1 | Above the bath or shower up to 2.25 m | Fixed equipment suitable for the zone |
| 2 | 0.6 m beyond zone 1 | No ordinary sockets or switches |
| Outside the zones | — | Sockets allowed, type A 30 mA RCD |
Is there a minimum number of sockets in Finland?
No binding minimum was found. The ST cards (ST-kortisto) published by Sähköinfo give guidance on socket placement and heights (ST 51.22), and building contracts often set equipment levels, but SFS 6000 itself does not require a number of sockets per room. Circuia therefore sets no socket minimum for Finland; plan by use, with several double sockets per bedroom and living room and enough outlets above the kitchen worktop.
Who may do the work: Tukes, contractors and the käyttöönottotarkastus
In Finland, electrical installation work is carried out by an electrical contractor (sähköurakoitsija) registered with Tukes, with a qualified person responsible for the work. Before an installation is used, the contractor performs a commissioning inspection (käyttöönottotarkastus): a visual inspection, measurements and tests, recorded in an inspection report (pöytäkirja). This applies to every job, small or large.
| Inspection | When | Who |
|---|---|---|
| Käyttöönottotarkastus (commissioning inspection) | Every installation job, before use | The contractor, with a written report |
| Varmennustarkastus (verification inspection) | Residential buildings with more than 2 dwellings; other installations with a main fuse above 35 A | An independent inspector, ordered by the contractor |
| Single-family house, 3 × 25 A | Commissioning inspection only, normally no verification inspection | The contractor |
Planning an SFS 6000 installation with Circuia
Choose Finland when you create the project. The editor spreads circuits over three phases, uses 10 A on 1.5 mm² for lighting and ordinary sockets and 16 A on 2.5 mm² for the kitchen and appliances, puts sockets and lighting behind at least 2 type A 30 mA RCDs, flags type AC devices, informs above 6 circuits per RCD and flags a main fuse above 35 A, which calls for a verification inspection. The circuit list, single-line diagram and bill of materials follow.
Open the editor set up for Finland (free, in your browser). Neighbouring countries: Sweden, Norway, Denmark, or the overview of all standards.
Common mistakes
- Fitting type AC RCDs where SFS 6000 requires type A.
- Leaving outdoor lighting of a dwelling without 30 mA RCD protection.
- Protecting 1.5 mm² cable in wall conduit at 16 A: Finnish practice is 10 A.
- Putting too many circuits on one RCD, so that normal leakage currents cause nuisance tripping.
- Adding a new unearthed socket to an old installation.
- Energising an installation before the commissioning inspection and its report.
Frequently asked questions
What is the current version of SFS 6000?
Which circuits need an RCD in Finland?
What is a käyttöönottotarkastus?
Does a new house in Finland need a third-party inspection?
Can I do my own electrical installation work in Finland?
Does Circuia certify an installation to SFS 6000?
Design aid
Design the installation with this country's rules
Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.
Written by
Circuia team
Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.
Published · updated
Sources
Sources used for this page, official texts first:
- Finlex — Electrical Safety Act 1135/2016 (English translation)
- Tukes — electrical installations
- Tukes — commissioning-stage inspections of electrical installations
- SESKO — SFS 6000 renewal 2022
- SESKO — RCD protection of EV charging stations
- linja-aho.fi — when did RCDs become mandatory
- STUL — socket requirements in the renewed standard
- SKT-säätiö — leakage currents and RCDs
Related pages
- OverviewElectrical wiring standards in Europe, country by countryHome wiring rules explained for the UK (BS 7671), Ireland (I.S. 10101), Norway, Sweden, Denmark and Finland, with the Circuia editor for each country.
- GuideSS 436 40 00 explained: Sweden's wiring rules for homes (Elinstallationsreglerna)SS 436 40 00 edition 4 for Swedish homes: elsäkerhetslagen, authorised electricians, 30 mA RCDs, 10 A on 1.5 mm², three-phase supply and egenkontroll.
- GuideNEK 400:2026 explained: Norway's wiring rules for homes, IT network includedNEK 400:2026 for Norwegian homes: the 230 V IT network, one RCD per circuit, stove guards, socket minimums, 30 % spare space and the samsvarserklæring.
- GuideDanish wiring rules explained: DS/HD 60364 and the installation order BEK 1082Denmark's wiring rules for homes: BEK 1082 and DS/HD 60364, TT earthing, 30 mA type A RCDs, 13 A sockets, one socket per 4 m² and authorised electricians.
- CircuiaPricing: free, Project Pass €39, Pro €49/monthCircuia plans: Free to explore, Project Pass at €39 incl. VAT for a homeowner project, Pro at €49 excl. VAT/month and Team at €129 excl. VAT/month for electricians. 14-day trial.
- CircuiaCircuia: AI wiring plans to BS 7671 and EU standardsDraw your home or ask the AI: Circuia designs circuits and the consumer unit, checked against BS 7671, I.S. 10101 and the rules of 17 European countries.