Standard · Ireland
I.S. 10101 explained: Ireland's National Rules for Electrical Installations in homes
I.S. 10101, the NSAI National Rules for Electrical Installations (5th edition, 2020), is the wiring standard for homes in the Republic of Ireland. The current text is I.S. 10101:2020+A1:2024. It requires 30 mA RCDs on socket and lighting circuits, limits 1.5 mm² lighting circuits to 6 A, and new circuits must be installed and certified by a Safe Electric Registered Electrical Contractor.
Updated on Last checked I.S. 10101:2020+A1:2024 · beta
Key facts
- 01I.S. 10101:2020 was published on 6 March 2020 and replaced ET 101:2008. It became mandatory for new designs on 1 October 2020 and for all certification on 1 April 2022.
- 02Lighting circuits in dwellings need 30 mA RCD protection (411.3.4), and type AC RCDs are not recommended in new installations (531.3.3).
- 03Lighting protection: 6 A on 1.5 mm² and 10 A on 2.5 mm², where 10 A on 1.5 mm² was the usual choice under ET 101.
- 04A standard ESB Networks connection is 12 kVA single-phase, with the customer's main protection at 63 A or less (enhanced: 16 kVA / 80 A).
- 05New circuits, consumer-unit changes and work in bathrooms are Restricted Electrical Works: only a Registered Electrical Contractor may do them and issue the Completion Certificate.
What is I.S. 10101 and is it the law in Ireland?
I.S. 10101, “National Rules for Electrical Installations”, is published by the National Standards Authority of Ireland (NSAI). It is the fifth edition of the Irish wiring rules and replaced ET 101:2008. Like BS 7671 in the UK and most European wiring standards, it is built on the international IEC / HD 60364 series, with Irish national choices on top.
A standard is not an Act, but in practice I.S. 10101 is compulsory for anyone certifying domestic work. Under the Electricity Regulation Act 1999 (as amended) and the decisions of the Commission for Regulation of Utilities (CRU), “Restricted Electrical Works” may only be carried out by a Registered Electrical Contractor (REC). The CRU's designated body, Safe Electric (previously known as RECI), registers these contractors and requires every certificate they issue to show compliance with I.S. 10101.
| Step | Date | What it means |
|---|---|---|
| I.S. 10101:2020 published | 6 March 2020 | 5th edition, replaces ET 101:2008 |
| Design to I.S. 10101 allowed | 1 April 2020 | Designers could switch early |
| Mandatory for new designs | 1 October 2020 | Every new design follows I.S. 10101 |
| All certification to I.S. 10101 | 1 April 2022 | End of pre-connection certification to the old rules |
| Amendment A1:2024 (consolidated) | September 2024 | Section 722 (EV charging) rewritten, new section 718, energy efficiency (Chapter 8) |
| Corrigendum AC2:2025 | April 2025 | Correction of Table 6E1 |
ESB Networks supply and earthing: 12 kVA and TN-C-S
Irish homes are supplied at 230 V single-phase, 50 Hz. The rules of connection are set by the ESB Networks National Code of Practice for Customer Interface (version 6.2, June 2025), which every installer must follow. The standard domestic connection has a Maximum Import Capacity (MIC) of 12 kVA, and the customer's main protective device may not exceed 63 A. The meter box on the outside wall is a standard 600 × 400 × 155 mm enclosure with its bottom 1,000 to 1,200 mm above finished ground level.
| Maximum Import Capacity | Connection | Maximum customer protection |
|---|---|---|
| 12 kVA | Single-phase, standard | 63 A |
| 16 kVA | Single-phase, enhanced | 80 A |
| 20 kVA | Single-phase, special | 100 A |
| 29 kVA | Single-phase, special | 125 A |
| 49 kVA | Three-phase | 80 A |
TN-C-S is the standard earthing arrangement for every new low-voltage ESB connection: the customer's main protective conductor is linked to the network neutral at the main supply point, at a single point, and the main earthing terminal sits outside the sealed ESB enclosure. Many existing homes are TT, with their own earth electrode; a REC can convert them to TN-C-S where the network equipment allows it, without breaking the ESB seals, and must certify the change.
Final circuits: radials, rings, lighting and cookers
Ireland uses the same 13 A fused plug and socket system as the UK (I.S. 401 plugs and I.S. 411 sockets, derived from BS 1363). The circuit layouts are therefore familiar to anyone who knows BS 7671, with one difference in habit: most Irish socket circuits are 20 A radials in 2.5 mm² cable, and the ring final circuit, standard in Britain, is used less often.
I.S. 10101 is a paid NSAI document and its domestic circuit rules (Annex 55A) are not publicly summarised. Apart from the lighting rule, which three Irish sources agree on, the values below are usual practice reported by Irish distributors and installers, used by Circuia as defaults and flagged for confirmation.
| Circuit | Protective device | Cable | Status of the value |
|---|---|---|---|
| Lighting | 6 A | 1.5 mm² | I.S. 10101 change reported by Kempston, Meteor and Hager |
| Lighting (larger cable) | 10 A | 2.5 mm² | Same sources |
| Socket radial (most common) | 20 A | 2.5 mm² | Usual practice; floor area limit not confirmed (Circuia assumes 50 m², the UK value) |
| Ring final circuit | 32 A only | 2.5 mm² | Allowed; 100 m² area reported but not confirmed |
| Cooker (via cooker control unit) | 32 A | 6 mm² | Usual; 40 A / 10 mm² for large cookers; above 10 kW the circuit must be calculated |
| Immersion heater | 16 A | 2.5 mm² | Usual; dedicated circuit, never on a ring |
| Electric shower | 40 A or 45 A | 10 mm² | Usual; dedicated circuit, check the 12 kVA MIC |
| EV charger | 32 A | Sized to the length (6 mm² or more) | Dedicated circuit, see the EV section |
- Rings are allowed at 32 A in 2.5 mm² (no 20 A rings). Spurs and fused connection units follow the same logic as in the UK, but that has not been confirmed against Annex 55A.
- Cookers above 10 kW must have their circuit calculated (Annex 55A rule 3.3, cited by Safe Electric), and the cooker isolator must be able to switch the full load.
- Cables must meet the fire-reaction class Dca-s2,d2,a2 at least (I.S. EN 50575, regulation 527).
RCDs, AFDDs and surge protection under I.S. 10101
The most visible change in 2020 was 30 mA RCD protection for lighting circuits in dwellings (411.3.4), on top of the long-standing requirement for socket-outlets up to 32 A (411.3.3). In practice a new Irish consumer unit protects every final circuit, most often with one RCBO per circuit or a “dual RCBO” for lighting, as manufacturers recommend.
| Device | Rule | Clause / source |
|---|---|---|
| 30 mA RCD, sockets up to 32 A | Required | 411.3.3 |
| 30 mA RCD, lighting in dwellings | Required since I.S. 10101:2020 | 411.3.4 |
| RCD type | Type AC not recommended in new work; use type A (F or B where the load needs it) | 531.3.3 |
| AFDD (arc fault detection, IEC 62606) | Recommended, not mandatory: sleeping accommodation, timber buildings, combustible stores, irreplaceable goods | 421.1.7 |
| SPD (surge protection) | Required where consequences are serious; for a house, assessed. Many installers fit one as standard | 443.4, section 534 |
| RCD on a micro-generator (PV) input | Changed from 30 mA to 100 mA by A1:2024 | 551.9.3 |
Two points remain open in public sources: whether every bathroom circuit and every cable buried less than 50 mm in a wall must be RCD-protected (as in the UK and HD 60364), and whether an SPD is effectively mandatory in a single house. Circuia assumes RCD protection everywhere and adds a type 2 SPD to the board by default, which is the cautious reading.
Bathrooms and shower rooms (Section 701)
Irish bathrooms follow the zone system of HD 60364-7-701, as in the UK. The dimensions below come from secondary Irish sources and match the harmonised document; the distance for 230 V sockets is where Ireland is reported to differ from the UK, and it is the least certain value on this page.
| Item | Value | Confidence |
|---|---|---|
| Zone 0 | Inside the bath or shower tray | Harmonised (HD 60364-7-701) |
| Zone 1 | Above the bath or tray up to 2.25 m from the floor | Harmonised; Irish sources secondary |
| Zone 2 | 0.6 m beyond zone 1 | Harmonised; Irish sources secondary |
| 230 V socket-outlets | Reported as not allowed within 3 m of zone 1 (UK: 2.5 m) | Low: one secondary source; Circuia applies it as the conservative choice |
| Shaver supply unit (EN 61558-2-5) | Allowed | Secondary sources |
| RCD for every circuit of the room | 30 mA | Expected (as HD 60364-7-701), not confirmed |
Consumer unit (distribution board) rules
- The board complies with I.S. EN 61439-1 and -3. The enclosure may be metal or non-metallic material that passes the glow-wire test of IEC 60695-2-11 (530.6.1). Unlike the UK, there is no blanket “non-combustible” rule.
- The top of the highest protective device must be no more than 2.15 m above the floor (reported by two Irish distributors).
- The main isolator switches both line and neutral on a single-phase domestic board.
- The main protection stays within the MIC: 63 A on a standard 12 kVA connection.
Neither I.S. 10101 (as publicly summarised) nor the Irish Building Regulations set a minimum number of sockets or lighting points per room. Plan by use: several double sockets per bedroom and living room, a generous number above the kitchen worktop, and dedicated outlets for fixed appliances.
EV chargers: Section 722 and the ESB 12 kVA connection
- Section 722 was entirely rewritten by A1:2024 (wired and wireless charging, RCD selectivity between the charger and the upstream devices).
- Each charger has its own circuit and RCD: type A is accepted when the charger has built-in 6 mA DC detection, otherwise type B.
- On a TN-C-S supply, an outdoor charger needs protection against a broken PEN conductor: either a dedicated earth electrode (TT) or a charger with certified open-PEN detection. The exact I.S. 10101 thresholds were not available to us.
- On a standard 12 kVA connection, a charger up to 32 A needs load management keeping the home within its MIC, or an application to ESB Networks for a higher MIC (National Code of Practice, Annex I).
Safe Electric, Registered Electrical Contractors and the Completion Certificate
Ireland does not use a third-party inspection before connection. Instead, the REC's Qualified Certifier self-certifies the work on a Safe Electric Completion Certificate, and ESB Networks connects a new installation only after it has received the validated certificate. Certificates are issued electronically.
| Work or document | Who / when |
|---|---|
| Restricted Electrical Works: new installation or new circuits, any change to the consumer unit, work in special locations (bathrooms, PV, EV charging), Periodic Inspection Reports | Registered Electrical Contractor only |
| Minor works: like-for-like replacement of switches, sockets or light fittings; adding a point to an existing circuit | No REC or certificate legally required (a customer may ask for one) |
| Completion Certificate No. 1 | New installation under 50 kVA connected to the ESB network (a new house) |
| Completion Certificate No. 2 | New installation of 50 kVA or more |
| Completion Certificate No. 3 | Alterations and additions to an existing installation |
| Pre-connection / post-connection certificates | Before energisation, then with the test results after ESB connects |
| Periodic Inspection Report (PIR) | Report on an existing installation, by a REC; commonly advised every 5 years or change of tenant for lettings, 10 years or change of owner for owner-occupiers |
Planning an I.S. 10101 installation with Circuia
Choose Ireland when you create the project. The editor then wires sockets as 20 A radials in 2.5 mm² by default (rings of 32 A are accepted and checked), limits lighting to 6 A on 1.5 mm², proposes RCBOs with a type 2 SPD, checks the bathroom distances, flags bedroom circuits for an AFDD and warns when an EV charger or a second shower may exceed the 12 kVA MIC. The circuit schedule, single-line diagram and bill of materials follow, ready to hand to your REC.
Open the editor set up for Ireland (free, in your browser). Working in Northern Ireland or Great Britain? See the BS 7671 guide and the overview of all standards.
Common mistakes
- Protecting 1.5 mm² lighting circuits at 10 A, as under ET 101: I.S. 10101 practice is 6 A.
- Leaving lighting circuits without 30 mA RCD protection in a new home.
- Fitting type AC RCDs in a new installation.
- Adding an EV charger or a second electric shower on a 12 kVA connection without load control or a MIC increase.
- Using the TN-C-S earth for an outdoor EV charger without open-PEN protection or an earth electrode.
- Replacing a consumer unit or adding a circuit without a REC and a Completion Certificate.
- Assuming UK bathroom distances apply unchanged: check the Irish value with your REC.
Frequently asked questions
What is the current version of I.S. 10101?
Do lighting circuits need an RCD in Ireland?
Why are lighting circuits 6 A on 1.5 mm² cable?
What is a Safe Electric cert?
Can I change my own consumer unit in Ireland?
Can I install an EV charger on a standard 12 kVA supply?
Does Circuia certify an installation to I.S. 10101?
Design aid
Design the installation with this country's rules
Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.
Written by
Circuia team
Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.
Published · updated
Sources
Sources used for this page, official texts first:
- NSAI — National Wiring Rules FAQs (I.S. 10101)
- Safe Electric — I.S. 10101 transition
- Safe Electric — I.S. 10101 summary of key changes
- Safe Electric — controlled and restricted electrical works
- Safe Electric — certificates
- Safe Electric — Periodic Inspection Reports
- ESB Networks — National Code of Practice for Customer Interface v6.2 (June 2025)
- ESB Networks — certification process
- Engineers Ireland — I.S. 10101:2020+A1:2024/AC2:2025 overview
- electric.ie — I.S. 10101 bitesize guide (Hager)
- Kempston Controls — I.S. 10101 bitesize guide
Related pages
- OverviewElectrical wiring standards in Europe, country by countryHome wiring rules explained for the UK (BS 7671), Ireland (I.S. 10101), Norway, Sweden, Denmark and Finland, with the Circuia editor for each country.
- GuideBS 7671 explained: the UK wiring regulations for homes (18th Edition, A4:2026)BS 7671:2018+A4:2026 for homes: ring and radial circuits, RCD, AFDD and SPD rules, bathroom zones, EV charging, consumer units and Part P certification.
- CircuiaPricing: free, Project Pass €39, Pro €49/monthCircuia plans: Free to explore, Project Pass at €39 incl. VAT for a homeowner project, Pro at €49 excl. VAT/month and Team at €129 excl. VAT/month for electricians. 14-day trial.
- CircuiaCircuia: AI wiring plans to BS 7671 and EU standardsDraw your home or ask the AI: Circuia designs circuits and the consumer unit, checked against BS 7671, I.S. 10101 and the rules of 17 European countries.