I.S. 10101 explained: Ireland's National Rules for Electrical Installations in homes

I.S. 10101, the NSAI National Rules for Electrical Installations (5th edition, 2020), is the wiring standard for homes in the Republic of Ireland. The current text is I.S. 10101:2020+A1:2024. It requires 30 mA RCDs on socket and lighting circuits, limits 1.5 mm² lighting circuits to 6 A, and new circuits must be installed and certified by a Safe Electric Registered Electrical Contractor.

Updated on Last checked I.S. 10101:2020+A1:2024 · beta

Key facts

  • 01I.S. 10101:2020 was published on 6 March 2020 and replaced ET 101:2008. It became mandatory for new designs on 1 October 2020 and for all certification on 1 April 2022.
  • 02Lighting circuits in dwellings need 30 mA RCD protection (411.3.4), and type AC RCDs are not recommended in new installations (531.3.3).
  • 03Lighting protection: 6 A on 1.5 mm² and 10 A on 2.5 mm², where 10 A on 1.5 mm² was the usual choice under ET 101.
  • 04A standard ESB Networks connection is 12 kVA single-phase, with the customer's main protection at 63 A or less (enhanced: 16 kVA / 80 A).
  • 05New circuits, consumer-unit changes and work in bathrooms are Restricted Electrical Works: only a Registered Electrical Contractor may do them and issue the Completion Certificate.

What is I.S. 10101 and is it the law in Ireland?

I.S. 10101, “National Rules for Electrical Installations”, is published by the National Standards Authority of Ireland (NSAI). It is the fifth edition of the Irish wiring rules and replaced ET 101:2008. Like BS 7671 in the UK and most European wiring standards, it is built on the international IEC / HD 60364 series, with Irish national choices on top.

A standard is not an Act, but in practice I.S. 10101 is compulsory for anyone certifying domestic work. Under the Electricity Regulation Act 1999 (as amended) and the decisions of the Commission for Regulation of Utilities (CRU), “Restricted Electrical Works” may only be carried out by a Registered Electrical Contractor (REC). The CRU's designated body, Safe Electric (previously known as RECI), registers these contractors and requires every certificate they issue to show compliance with I.S. 10101.

I.S. 10101 editions and key dates
StepDateWhat it means
I.S. 10101:2020 published6 March 20205th edition, replaces ET 101:2008
Design to I.S. 10101 allowed1 April 2020Designers could switch early
Mandatory for new designs1 October 2020Every new design follows I.S. 10101
All certification to I.S. 101011 April 2022End of pre-connection certification to the old rules
Amendment A1:2024 (consolidated)September 2024Section 722 (EV charging) rewritten, new section 718, energy efficiency (Chapter 8)
Corrigendum AC2:2025April 2025Correction of Table 6E1
Sources: Safe Electric (transition dates), Engineers Ireland (A1:2024 / AC2:2025). The date from which A1:2024 becomes mandatory has not been confirmed from public sources: check with Safe Electric.

ESB Networks supply and earthing: 12 kVA and TN-C-S

Irish homes are supplied at 230 V single-phase, 50 Hz. The rules of connection are set by the ESB Networks National Code of Practice for Customer Interface (version 6.2, June 2025), which every installer must follow. The standard domestic connection has a Maximum Import Capacity (MIC) of 12 kVA, and the customer's main protective device may not exceed 63 A. The meter box on the outside wall is a standard 600 × 400 × 155 mm enclosure with its bottom 1,000 to 1,200 mm above finished ground level.

ESB Networks domestic connection sizes (National Code of Practice, Table 5)
Maximum Import CapacityConnectionMaximum customer protection
12 kVASingle-phase, standard63 A
16 kVASingle-phase, enhanced80 A
20 kVASingle-phase, special100 A
29 kVASingle-phase, special125 A
49 kVAThree-phase80 A
Source: ESB Networks National Code of Practice for Customer Interface v6.2 (26/06/2025).

TN-C-S is the standard earthing arrangement for every new low-voltage ESB connection: the customer's main protective conductor is linked to the network neutral at the main supply point, at a single point, and the main earthing terminal sits outside the sealed ESB enclosure. Many existing homes are TT, with their own earth electrode; a REC can convert them to TN-C-S where the network equipment allows it, without breaking the ESB seals, and must certify the change.

Final circuits: radials, rings, lighting and cookers

Ireland uses the same 13 A fused plug and socket system as the UK (I.S. 401 plugs and I.S. 411 sockets, derived from BS 1363). The circuit layouts are therefore familiar to anyone who knows BS 7671, with one difference in habit: most Irish socket circuits are 20 A radials in 2.5 mm² cable, and the ring final circuit, standard in Britain, is used less often.

I.S. 10101 is a paid NSAI document and its domestic circuit rules (Annex 55A) are not publicly summarised. Apart from the lighting rule, which three Irish sources agree on, the values below are usual practice reported by Irish distributors and installers, used by Circuia as defaults and flagged for confirmation.

Usual final circuits in an Irish home (type B MCB or RCBO, copper twin and earth)
CircuitProtective deviceCableStatus of the value
Lighting6 A1.5 mm²I.S. 10101 change reported by Kempston, Meteor and Hager
Lighting (larger cable)10 A2.5 mm²Same sources
Socket radial (most common)20 A2.5 mm²Usual practice; floor area limit not confirmed (Circuia assumes 50 m², the UK value)
Ring final circuit32 A only2.5 mm²Allowed; 100 m² area reported but not confirmed
Cooker (via cooker control unit)32 A6 mm²Usual; 40 A / 10 mm² for large cookers; above 10 kW the circuit must be calculated
Immersion heater16 A2.5 mm²Usual; dedicated circuit, never on a ring
Electric shower40 A or 45 A10 mm²Usual; dedicated circuit, check the 12 kVA MIC
EV charger32 ASized to the length (6 mm² or more)Dedicated circuit, see the EV section
Voltage drop: Circuia applies 4 % to every circuit (the figure Safe Electric cites from ET 101); the I.S. 10101 limit has not been confirmed.
  • Rings are allowed at 32 A in 2.5 mm² (no 20 A rings). Spurs and fused connection units follow the same logic as in the UK, but that has not been confirmed against Annex 55A.
  • Cookers above 10 kW must have their circuit calculated (Annex 55A rule 3.3, cited by Safe Electric), and the cooker isolator must be able to switch the full load.
  • Cables must meet the fire-reaction class Dca-s2,d2,a2 at least (I.S. EN 50575, regulation 527).

RCDs, AFDDs and surge protection under I.S. 10101

The most visible change in 2020 was 30 mA RCD protection for lighting circuits in dwellings (411.3.4), on top of the long-standing requirement for socket-outlets up to 32 A (411.3.3). In practice a new Irish consumer unit protects every final circuit, most often with one RCBO per circuit or a “dual RCBO” for lighting, as manufacturers recommend.

Protective devices in a new Irish home
DeviceRuleClause / source
30 mA RCD, sockets up to 32 ARequired411.3.3
30 mA RCD, lighting in dwellingsRequired since I.S. 10101:2020411.3.4
RCD typeType AC not recommended in new work; use type A (F or B where the load needs it)531.3.3
AFDD (arc fault detection, IEC 62606)Recommended, not mandatory: sleeping accommodation, timber buildings, combustible stores, irreplaceable goods421.1.7
SPD (surge protection)Required where consequences are serious; for a house, assessed. Many installers fit one as standard443.4, section 534
RCD on a micro-generator (PV) inputChanged from 30 mA to 100 mA by A1:2024551.9.3
Sources: Safe Electric summary of key changes, electric.ie (Hager), Kempston Controls, Engineers Ireland.

Two points remain open in public sources: whether every bathroom circuit and every cable buried less than 50 mm in a wall must be RCD-protected (as in the UK and HD 60364), and whether an SPD is effectively mandatory in a single house. Circuia assumes RCD protection everywhere and adds a type 2 SPD to the board by default, which is the cautious reading.

Bathrooms and shower rooms (Section 701)

Irish bathrooms follow the zone system of HD 60364-7-701, as in the UK. The dimensions below come from secondary Irish sources and match the harmonised document; the distance for 230 V sockets is where Ireland is reported to differ from the UK, and it is the least certain value on this page.

Bathroom zones and sockets in Ireland (as used by Circuia)
ItemValueConfidence
Zone 0Inside the bath or shower trayHarmonised (HD 60364-7-701)
Zone 1Above the bath or tray up to 2.25 m from the floorHarmonised; Irish sources secondary
Zone 20.6 m beyond zone 1Harmonised; Irish sources secondary
230 V socket-outletsReported as not allowed within 3 m of zone 1 (UK: 2.5 m)Low: one secondary source; Circuia applies it as the conservative choice
Shaver supply unit (EN 61558-2-5)AllowedSecondary sources
RCD for every circuit of the room30 mAExpected (as HD 60364-7-701), not confirmed
Any electrical work in a bathroom is Restricted Electrical Works (special location, Chapter 7): a REC must do it.

Consumer unit (distribution board) rules

  • The board complies with I.S. EN 61439-1 and -3. The enclosure may be metal or non-metallic material that passes the glow-wire test of IEC 60695-2-11 (530.6.1). Unlike the UK, there is no blanket “non-combustible” rule.
  • The top of the highest protective device must be no more than 2.15 m above the floor (reported by two Irish distributors).
  • The main isolator switches both line and neutral on a single-phase domestic board.
  • The main protection stays within the MIC: 63 A on a standard 12 kVA connection.

Neither I.S. 10101 (as publicly summarised) nor the Irish Building Regulations set a minimum number of sockets or lighting points per room. Plan by use: several double sockets per bedroom and living room, a generous number above the kitchen worktop, and dedicated outlets for fixed appliances.

EV chargers: Section 722 and the ESB 12 kVA connection

  • Section 722 was entirely rewritten by A1:2024 (wired and wireless charging, RCD selectivity between the charger and the upstream devices).
  • Each charger has its own circuit and RCD: type A is accepted when the charger has built-in 6 mA DC detection, otherwise type B.
  • On a TN-C-S supply, an outdoor charger needs protection against a broken PEN conductor: either a dedicated earth electrode (TT) or a charger with certified open-PEN detection. The exact I.S. 10101 thresholds were not available to us.
  • On a standard 12 kVA connection, a charger up to 32 A needs load management keeping the home within its MIC, or an application to ESB Networks for a higher MIC (National Code of Practice, Annex I).

Safe Electric, Registered Electrical Contractors and the Completion Certificate

Ireland does not use a third-party inspection before connection. Instead, the REC's Qualified Certifier self-certifies the work on a Safe Electric Completion Certificate, and ESB Networks connects a new installation only after it has received the validated certificate. Certificates are issued electronically.

Restricted works, minor works and the Safe Electric certificates
Work or documentWho / when
Restricted Electrical Works: new installation or new circuits, any change to the consumer unit, work in special locations (bathrooms, PV, EV charging), Periodic Inspection ReportsRegistered Electrical Contractor only
Minor works: like-for-like replacement of switches, sockets or light fittings; adding a point to an existing circuitNo REC or certificate legally required (a customer may ask for one)
Completion Certificate No. 1New installation under 50 kVA connected to the ESB network (a new house)
Completion Certificate No. 2New installation of 50 kVA or more
Completion Certificate No. 3Alterations and additions to an existing installation
Pre-connection / post-connection certificatesBefore energisation, then with the test results after ESB connects
Periodic Inspection Report (PIR)Report on an existing installation, by a REC; commonly advised every 5 years or change of tenant for lettings, 10 years or change of owner for owner-occupiers
Sources: Safe Electric (certificates, restricted and minor works, PIR), ESB Networks certification process. Whether a PIR is a legal obligation for rented homes has not been confirmed.

Planning an I.S. 10101 installation with Circuia

Choose Ireland when you create the project. The editor then wires sockets as 20 A radials in 2.5 mm² by default (rings of 32 A are accepted and checked), limits lighting to 6 A on 1.5 mm², proposes RCBOs with a type 2 SPD, checks the bathroom distances, flags bedroom circuits for an AFDD and warns when an EV charger or a second shower may exceed the 12 kVA MIC. The circuit schedule, single-line diagram and bill of materials follow, ready to hand to your REC.

Open the editor set up for Ireland (free, in your browser). Working in Northern Ireland or Great Britain? See the BS 7671 guide and the overview of all standards.

Common mistakes

  • Protecting 1.5 mm² lighting circuits at 10 A, as under ET 101: I.S. 10101 practice is 6 A.
  • Leaving lighting circuits without 30 mA RCD protection in a new home.
  • Fitting type AC RCDs in a new installation.
  • Adding an EV charger or a second electric shower on a 12 kVA connection without load control or a MIC increase.
  • Using the TN-C-S earth for an outdoor EV charger without open-PEN protection or an earth electrode.
  • Replacing a consumer unit or adding a circuit without a REC and a Completion Certificate.
  • Assuming UK bathroom distances apply unchanged: check the Irish value with your REC.

Frequently asked questions

What is the current version of I.S. 10101?

I.S. 10101:2020, the 5th edition of the National Rules for Electrical Installations, published by NSAI on 6 March 2020. It was amended by A1:2024 (consolidated text published in September 2024, including a rewritten EV section 722) and corrected by AC2:2025. It replaced ET 101:2008, and all certification has been to I.S. 10101 since 1 April 2022.

Do lighting circuits need an RCD in Ireland?

Yes. Since I.S. 10101:2020, regulation 411.3.4 requires 30 mA additional protection for lighting circuits in dwellings, as well as for socket-outlets up to 32 A. Type AC RCDs are not recommended in new installations. Most new Irish boards use one RCBO per circuit or dual RCBOs for lighting.

Why are lighting circuits 6 A on 1.5 mm² cable?

Under ET 101 a 10 A breaker on 1.5 mm² cable was common. Irish distributors and Hager report that I.S. 10101 practice is 6 A on 1.5 mm² and 10 A on 2.5 mm². The exact clause, and whether it depends on the installation method (for example cable in thermal insulation), should be confirmed in the standard.

What is a Safe Electric cert?

It is the Completion Certificate a Registered Electrical Contractor issues through Safe Electric, the CRU's designated body. Certificate No. 1 covers a new installation under 50 kVA, No. 3 alterations and additions. ESB Networks connects a new installation only once the validated certificate is received. Minor like-for-like replacements do not need one.

Can I change my own consumer unit in Ireland?

No. Any modification, replacement or addition to a distribution board is Restricted Electrical Works and may only be done by a Registered Electrical Contractor, who then issues a Completion Certificate. The same applies to new circuits and to work in bathrooms. Homeowners may only do minor works such as like-for-like replacements, and should never work on live circuits.

Can I install an EV charger on a standard 12 kVA supply?

Yes, a charger up to 32 A, provided load management keeps the home within its 12 kVA MIC, or after ESB Networks approves a higher MIC. It needs its own circuit and RCD (type A with 6 mA DC detection in the charger, otherwise type B) and, outdoors on TN-C-S, open-PEN protection or an earth electrode.

Does Circuia certify an installation to I.S. 10101?

No. Circuia checks a plan against its Ireland rules pack, which is in beta and built from public sources, and produces the circuit schedule, single-line diagram and bill of materials. Only a Registered Electrical Contractor can install, test and certify the work with a Safe Electric Completion Certificate.

Design aid

Design the installation with this country's rules

Draw the home or describe it to the AI: Circuia places the points, checks the country's rules in real time and generates the consumer unit, single-line diagram and bill of materials.

Open the editor for this country

Written by

Circuia team

Written by the Circuia team from the sources listed and from the editor's rules pack for this country: the values in the tables are the ones Circuia uses.

Published · updated

Related pages